46
Function Description
Table 37: Function Description — Outputs, All Versions, Except 750-637/000-004
Output
N1, N2
Table 38: Function Description — Outputs, Version 750-637/000-004 Only
Output
N1, N2
Manual
Version 1.6.1
Function
Cam output, 24 V, 0.5 A
0:
Counter value outside the set window.
1:
Counter value within the set window.
Function
Cam output, 24 V, 0.5 A
0:
Counter value outside the set window.
1:
Counter value within the set window.
Cams can be enabled and disabled globally. This guarantees
that no unexpected switching states occur during ongoing
operation due to changes of the windows.
All cam outputs are reset (output votlage 0 V) on loss of field
voltage.
When voltage is restored, all cams remain reset, regardless of
the previous switching state (output voltage 0 V).
The loss of voltage is reported to the control unit via a status
bit.
The cam windows must then be set anew.
Public
WAGO I/O System 750
750-637 Incremental Encoder Interfaces