3: Control Modules; 4: Relay Modules; 5: Multiple Input/Output Modules; 6: Intelligent Detectors - Honeywell Fire-Lite Alarms MS-9200 Wiring Manual

Intelligent control panel, slc
Table of Contents

Advertisement

Devices
1.4.3 Control Modules
Through the CMF-300 addressable control module, the control panel can selectively activate a Notification Appliance Circuit (NAC).
CMF-300-6 - Similar in operation to the CMF-300, except it can activate six (6) Class B or three (3) Class A NACs.
1.4.4 Relay Modules
The CRF-300 addressable relay module provides the control panel with a dry-contact output for activating a variety of auxiliary devices.
CRF-300-6 - Similar in operation to the CRF-300, except it provides six (6) Form-C relays.
1.4.5 Multiple Input/Output Modules
The CDRM-300 addressable multiple input/output module monitors two (2) Class B input devices and provides two (2) independent
Form-C relay contacts.
1.4.6 Intelligent Detectors
AD350 - A multi-criteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detec-
tion. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its
detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
AD355 - Multi-criteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detec-
tion. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its
detection parameters and alarm threshold depending on the ambient conditions it samples in its environment.
AD365 - Multi-criteria smoke sensor that combines a photoelectric sensing chamber and 135°F (57.2°C) fixed temperature heat detec-
tion. The sensor uses addressable communication to transmit smoke density and other information to the control panel. It adjusts its
detection parameters and alarm threshold depending on the ambient conditions it samples in its environment. This model is available in
ivory with -IV added to the model name. The ivory color model has the ability to work in CLIP mode. The standard white color func-
tions in LiteSpeed only.
CP350 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the 'ionization
principle'.
CP355 - Addressable ionization smoke detector which measures the level of combustion products in its chamber using the 'ionization
principle'.
D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air velocity rating is 500 to 4,000 feet per
minute.
D350PL -Addressable low flow photoelectric duct detector (D350PLA for Canada). The D350RPL includes an alarm relay
(D350RPLA for Canada). Low Flow refers to the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec).
D355PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to the air velocity rating of 100 to 4,000
feet per minute (0.5 to 20.32 m/sec).
D365PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to the air velocity rating of 100 to 4,000
feet per minute (0.5 to 20.32 m/sec).
1
H350
- An addressable detector using a thermistor sensing circuit for fast response. H350R incorporates a thermal rate of rise of 15°F
(9.4°C)/minute.
1
H355
- Addressable 135° fixed temperature heat detector using a thermistor sensing circuit for fast response. H355R incorporates a
thermal rate of rise of 15° F (9.4° C)/minute.
1
H355HT
- Addressable 190° fixed temperature heat detector using a thermistor sensing circuit for fast response.
1
H365
- Addressable 135° fixed temperature heat detector using a thermistor sensing circuit for fast response. H365R incorporates a
thermal rate of rise of 15° F (9.4° C)/minute. This model is available in ivory with -IV added to the model name. The ivory color model
has the ability to work in CLIP mode. The standard white color functions in LiteSpeed only.
1
H365HT
- Addressable 190° fixed temperature heat detector using a thermistor sensing circuit for fast response. This model is avail-
able in ivory with -IV added to the model name. The ivory color model has the ability to work in CLIP mode. The standard white color
functions in LiteSpeed only.
SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD350T
includes a 135° F fixed thermal sensor.
SD355 - Addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD355T
includes a 135° F fixed thermal sensor. The SD355R is a low profile, intelligent, photoelectric sensor that is remote test capable.
SD365 - Addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD365T
includes a 135° F fixed thermal sensor. The SD365R is a low profile, intelligent, photoelectric sensor that is remote test capable. For use
with DNR(W). This model is available in ivory with -IV added to the model name. The ivory color model has the ability to work in CLIP
mode. The standard white color functions in LiteSpeed only.
SD355CO - addressable device that provides both fire and carbon monoxide (CO) detection. It combines four separate sensing elements
in one unit (smoke, CO, light/flame, and heat) to sense multiple components of a fire. The detector's electrochemical sensing cell creates
a separate signal for life safety CO detection.
1. Addressable Heat Detectors are not compatible with the MS-9200(E).
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019