B.1 Introduction
NOTE: Surge protection is not required in Canadian applications.
There are three (3) primary surge protectors that are approved for use with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-
9600LS, MS-9600UDLS, and MS-9050UD.
DTK-2LVLP-F
SLCP-30
EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800) 727-9119
NOTE: For detailed information, refer to the Installation Instructions supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building.
Install primary protection only as shown in this document.
Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC
wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input
may be routed outside the building as shown below.
B.2 Installation
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use.
Locate on an available stud and secure with nut.
Unit is connected in series with the SLC Loop to protect the Control Panel.
Provide a common ground to eliminate the possibility of a differential in ground potentials.
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019

Appendix B: Surge Suppression

Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771 (727) 812-5000
Building #2
P
P = Primary
S = Secondary
P
Surge Suppressor
Primary devices meet
NEC Requirements
Building #1
P
FACP
S
S
P
Secondary devices meet
UL1459 (UL1950)