MMF-302 Wiring Diagrams
5.6.2 Wiring a NFPA Class A IDC with an MMF-302
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to "Setting
an SLC address for a Single Point Module" on page 33.
The figure below shows typical wiring for a supervised and power-limited NFPA Class A IDC using an MMF-302 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
24 VDC power must be provided from a UL listed power supply for fire protection use. This power is inherently supervised by the
module.
See "Power Considerations" on page 63 for information on 24 VDC power.
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
Two-wire
24 VDC Resettable power.
smoke
90 mA External 24 volt supply required
detectors
IDC
3.9K ELR
(supplied with module)
Figure 5.16 Typical Class A IDC Wiring with an MMF-302
SLC
MMF-302
Monitor Modules
41