Intelligent Detector Bases and Wireless Gateway
9.4 Wiring an Isolator Base
The B224BI Isolator Base will isolate its detector from short circuits that occur on the SLC connected at terminals 2 and 3. It will not
isolate its installed detector from short circuits that occur on the SLC connected at terminals 1 and 2. In Class X applications, the loss of
a single detector during a short circuit is not acceptable, and an isolator module must be installed as shown in the figure below.
Note: The "grid" pattern on the
redesigned B224BI mounting
plate has been removed for
illustration purposes only.
9.5 Wiring a Relay Base
Figure 9.3 shows typical wiring of a B224RB plug-in relay detector base connected to an SLC.
56
I300 Isolator Module
Figure 9.2 Wiring of a B224BI Isolator Base Mounting Plate
To next device
on SLC
+ -
+ -
SLC
Figure 9.3 Wiring of a B224RB Relay Base Mounting Plate
SLC Out
SLC In
Conduit
Note: The "grid" pattern on the
redesigned B224RB mounting
plate has been removed for
illustration purposes only.
Normally Closed
Common
Normally Open
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
Wiring an Isolator Base