NFPA Class B SLC Using Isolator Modules
A variation of a Class B operation using an ISO-6 isolator module to protect each branch of the SLC is shown below. Each terminal on
the ISO-6 acts as a single I300 module. Refer to Figure 4.2 for ISO-6 wiring and to Section 4.1 for limitations. Note that the ISO-6 can-
not accept two wires at one pin. Wire Class B SLC loops as shown in the figure below.
ISO-6
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
Out -
Out +
In -
Isolated Branch
In +
Isolated Branch
Isolated Branch
Control Panel
SLC
Figure 4.4 NFPA Class B SLC Using an ISO-6 Isolator Module
Two-wire Addressable Detector
Addressable Pull Station
SLC Circuits with Isolators