Section 9: Intelligent Detector Bases And Wireless Gateway; Description; Setting The Detector Address - Honeywell Fire-Lite Alarms MS-9200 Wiring Manual

Intelligent control panel, slc
Table of Contents

Advertisement

Section 9: Intelligent Detector Bases and Wireless Gateway

9.1 Description

The following bases provide connection between the SLC and these detector heads:
AD350 and AD355 Multi-criteria Photoelectric Smoke Detectors
CP350 and CP355 Ionization Smoke Detectors
H350, H350R, H355, H355R, H355HT, H365(-IV), H365R(-IV), H365HT(-IV) Thermal Detectors
SD350, SD350T, SD355, SD355T, SD365(-IV), and SD365T(-IV) Photoelectric Smoke Detectors
The B501(-WHITE/-BL/-IV), B210LP, and B300-6(-IV) bases are standard plug-in detector bases.
The B501BH, B501BHT, B501BH-2, B501BHT-2, B200S(-WH/-IV), B200S-LF(-WH/-IV), B200SR(-WH/-IV), and B200SR-LF(-
WH/-IV) Sounder Detector Bases include a horn that will sound when the sensor's visible LEDs are latched on for approximately 10
seconds.
On the MS-9200 Control Panel, the sounder will activate when the sensor's visible LEDs are latched on for approximately 10
seconds (Alarm Verification does not delay sounder).
If the MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, MS-9050UD, ES-50X, or ES-200X, Control Panel
is set with Alarm Verification ON (enabled), the sounder will activate at the end of the verification cycle, providing an alarm is
verified, approximately 10 seconds after the sensor's LEDs are latched on. If Alarm Verification is OFF (disabled), the sounder will
activate when the sensor's visible LEDs are latched on for approximately 10 seconds.
The B224RB(-WH/-IV) Relay Detector Base includes Form-C latching relay contacts for the control of an auxiliary function. The relay
operates 12 seconds (nominally) after activation of the sensor head remote annunciator output.
The B224BI(-WH/-IV) Isolator Detector Base prevents an entire communications loop from being disabled when a short circuit occurs.
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the ES-50X,
ES-200X, or MS-9200UDLS. The gateway can be powered by the SLC loop or by a regulated, external UL-listed, 24VDC power supply.
See Section 9.7.
NOTE: When using a Wireless Gateway on the SLC loop, the panel cannot have ANY modules (wired or wireless) in the address range
from 140 to 159.
For details about the wireless network and its devices, see the SWIFT™ Smart Wireless Integrated Fire Technology Instruction Manual
#LS10036-000FL-E.

9.2 Setting the Detector Address

Each intelligent detector is factory preset with an address of "00." To set an SLC address, use a common screwdriver to adjust the rotary
switches on the detector to the desired address (see "Setting an SLC address for a Single Point Module" on page 33). When finished,
mark the address in the place provided on the base and the detector.
54
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents