3: Mmf-300 Wiring For Emergency Alarm System Applications - Honeywell Fire-Lite Alarms MS-9200 Wiring Manual

Intelligent control panel, slc
Table of Contents

Advertisement

Monitor Modules
5.3.3 MMF-300 Wiring for Emergency Alarm System Applications
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to "Setting
an SLC address for a Single Point Module" on page 33.
The figure below shows typical wiring for a supervised and power-limited Emergency Signaling circuit using an MMF-300 module.
See "Power Considerations" on page 63 for information on supervising 24 VDC power.
See Section 6, "Control Modules" for instructions on using control modules as NACs on an SLC.
Refer to the Device Compatibility Document #15384 for compatible smoke detectors.
UL-listed Signaling
appliance such as the
Fire-Lite FSS-2400E
36
47K ELR
(supplied
with module)
IDC
Figure 5.11 Emergency Signaling Wiring with an MMF-300
SLC
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
MMF-300 Wiring Diagrams
-
+
-
+