Honeywell Fire-Lite Alarms MS-9200 Wiring Manual page 31

Intelligent control panel, slc
Table of Contents

Advertisement

Descriptions
MMF-302-6 Interface Module
This monitor module is intended to interface between the FACP and a conventional alarm system with up to six (6) Class B or three (3)
Class A IDCs containing normally open contact devices.
This monitor module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which
requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into cabinet.
Disable Address
Place shunt in:
Disable 1 position to disable highest module address
Disable 2 position to disable highest two module addresses
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
T1
T0
– +
– +
– +
– +
T6
T5
J1
BASE ADDRESS +0
BASE ADDRESS +1
BASE ADDRESS +2
Figure 5.4 MMF-302-6 Interface Module
T2
T3
– +
– +
– +
– +
BASE ADDRESS +3
BASE ADDRESS +4
Class B or Class A Select
Remove shunt for Class A circuits
Monitor Modules
T4
– +
– +
SW1
BASE ADDRESS +5
SLC Address
Set rotary switches to base
(first) address of modules
31