MMF-300 Wiring Diagrams
5.3.2 Wiring a NFPA Class A IDC with an MMF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address. Refer to "Set-
ting an SLC address for a Single Point Module" on page 33.
The figure below shows typical wiring for a supervised and power-limited NFPA Class A IDC using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See "Power Considerations" on page 63 for information on supervising 24 VDC power.
Manual pull
station
Heat
detector
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
24 VDC
Four-wire
Detector Base
IDC
Figure 5.10 Typical Class A IDC Wiring with an MMF-300
From
Supply
24 VDC Power
Filtered, Regulated,
Resettable
To Next IDC
or
Supervision Device
SLC
MMF-300
Monitor Modules