3: Ms-9200Udls (Software Version 3.0); 4: Ms-9200Ud & Ms-9200Udls (Versions 1 And 2); 5: Ms-9050Ud - Honeywell Fire-Lite Alarms MS-9200 Wiring Manual

Intelligent control panel, slc
Table of Contents

Advertisement

Wiring Requirements
2.4.3 MS-9200UDLS (Software Version 3.0)
TB1 provides two types of 24 VDC power; Nonresettable and Resettable, jumper selectable by JP4 and JP6.
TB10 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
2.4.4 MS-9200UD & MS-9200UDLS (Versions 1 and 2)
TB1 provides two types of 24 VDC power; Nonresettable and Resettable.
TB10 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
2.4.5 MS-9050UD
24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8.
TB2 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).
18
Nonresettable Power- jumper selectable by JP4
SLC Out
Figure 2.8 MS-9200UDLS (Rev 3) Terminal Blocks
Nonresettable Power
SLC Out
Figure 2.9 MS-9200UD & MS-9200UDLS (Rev 1 & 2) Terminal Blocks
SLC Out
Figure 2.10 MS-9050UD Terminal Block
Resettable Power-
jumper selectable by JP6
SLC
TB10
Connections for
Resettable
wire shield
Power
SLC
TB10
Connections for wire shield
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
Control Panel Terminal Blocks
Connections for
wire shield
SLC Return
SLC Return
SLC Return