List of Occupancy configuration Parameters

Config
parameter
Name
number
500
Occupancy
Source
501
Holiday default
days
502
Bypass default
minutes
503
Bypass time
adjust step
minutes
504
Allowed
overrides from
OFF
505
Allowed
overrides from
UNOCC
506
Allowed
overrides from
STANDBY
507
Allowed
overrides from
OCC
TR80 - Installation and Operation Guide
Type/
Range
Unit
(min-Max)
enum
0: Modbus only
1: Button only
2: Modbus & override from
button
days
1-45
minutes
10-1440
enum
0: 10 mins
1: 20 mins
2: 30 mins
3: 60 mins
bitmap
bit0: unused
bit1: unused
bit2: Allow override to
OCCUPIED
bit3: Allow override to OFF
bit4: Allow override to
HOLIDAY
bit5: Allow override to
UNOCC
bit6: Allow override to
STANDBY
bit7: Allow override to
BYPASS
bitmap
bitmap
bitmap
Default
Notes
0
0: Modbus only
(button disabled)
1: Button only (simple
mode, no override,
only occupied/
unoccupied switching
on WM)
2: Modbus with
override from button
(advanced mode)
7 days
180 mins
2
0
These registers used
to define which
override are available
in which occupancy
mode.
Short-press is
automatically
assigned to one of the
below, in order of
preference:
- OCC
- UNOCC
- BYPASS
144: HOL &
BYPASS
148: OCC, HOL
& BYPS
176: UNOCC,
HOL & BYPS