Hardware Installation
Installing 4-Wire Class A Smoke Detectors
Figure 3-15 illustrates how to install 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loops:
1. Up to two Class A 4-wire loops can be connected to the control panel at once.
2. Smoke power is supplied to each Class A loop as shown in Figure 3-15.
Air Products
PAM-2
Model 160150
Supervision
Module
Figure 3-15 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O
circuit number used. For example, Figure 3-15 uses I/O circuits 1, 2, 3 together and 4, 5, 6
together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred
to as point 4.
3.5.6

Auxiliary Power Configuration

Flexput circuits 1-6 on the control panel can be used as auxiliary power circuits. The
three types of auxiliary power available are:
Door Holder (see Section 3.5.6.1 for description)
Constant (see Section 3.5.6.2 for description)
Resettable (see Section 3.5.6.3 for description)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total
current for all Flexput circuits must not exceed 5A).
To configure a Flexput circuit as auxiliary power:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 3-16 for loca-
tion or Flexput circuits.
3-12
151153
Air Products
PAM-2
Model 160150
Supervision
Module