List Of Hvac Configuration Parameters - Honeywell TR80 Installation And Operating Manual

Wall module
Table of Contents

Advertisement

List of HVAC Configuration Parameters

Config
parameter
Name
number
200
Setpoint
style
201
Setpoint
minimum
202
Setpoint
maximum
203
Default
Setpoint
204
Fan type
205
EC Fan
speed
adjust step
size
206
Fan speed
low-limit
207
Fan speed
high limit
208
Fan UI
attributes
209
HvacMode
SelectionTy
pe
TR80 - Installation and Operation Guide
Type/
Range
Unit
(min-Max)
enum
0: absolute
1: relative
signed int
absolute mode: -50....+150
(°C / K)
relative mode: -15.......0
signed int
absolute mode: -50....+150
(°C / K)
relative mode: 0.......15
°C
10....30 °C
enum
0: no fan
1: Single speed fan
2: Two-speed fan
3: 3-speed fan
4: EC fan
enum
0: 1%
1 : 2%
2 : 5%
3: 10%
4: 20%
% or int
0-100 % for EC fans,
0-3 for others
% or int
0-100 %
0-3 for others
bitmap
Bit 0: Fan override (0: No
ovrd, 1: Allow ovrd)
Bit 1: Display of 1-stage
fan (0: 1 bar, 1: 3 bars)
Bit 2-16: reserved
enum
0: disabled
1: simple
2: advanced
Default
Notes
0: absolute
absolute: 10 °C
relative: -5 K
absolute: 30 °C
relative: +5 K
22 °C
3
3: 10%
For EC fans only
0
100
1
If fan override not allowed,
disable fan button but keep
speed indication & AUTO symbol
0
65