BEFORE INSTALLATION
All wiring must comply with local electrical codes and
ordinances or as specified on installation wiring diagrams.
Wall module wiring can be sized from 16 to 22 AWG (1.5 to
0.34 mm
), depending on the application. The maximum
2
length of wire from a device to a wall module is 1000 ft (305
m). Twisted-pair wire is recommended for wire runs longer
than 100 ft (30.5 m).
COVER DISASSEMBLY
The cover of the wall module is fixed in place using a tab
located on the underside of the unit; to disassemble the cover
and the sub-base, see Fig. 1.
2
LIFT
1
PRESS
Fig. 1. Cover disassembly
Table 1. Features of T7460 Versions
Sensor
Setpoint Bypass/ LED Fan switch
T7460A
-
T7460B
T7460C
T7460D
T7460E
T7460F
INSTALLATION
The T7460B,C,D,E,F packages include two setpoint dials. By
default, the "Celsius Relative" type is mounted. This can be
® U.S. Registered Trademark
Copyright © 2018 Honeywell Inc. • All Rights Reserved
easily replaced with the "Celsius Absolute" type by pulling the
one dial off and inserting the other one.
Mount the T7460A,B,C,D,E,F Wall Modules on an inside wall
approximately 54 in. (1.3 m) from the floor (or in the specified
location) to allow exposure to the average zone temperature.
NOTE: Maintain a mounting clearance of approx. 4 in.
The wall modules can be mounted on a 60-mm wall outlet box
using No. 6 (3.5-mm) screws or on a wall (see Fig. 2 and Fig.
5). When mounting directly on a wall, use the type of screws
appropriate for the wall material.
-
-
-
-
-
-
5-position
3-position
5-position
See Fig. 3 for mounting dimensions.
NOTE: Graphics depict E/F model. Dimensions are the
T7460A,B,C,D,E,F
INSTALLATION INSTRUCTIONS
(10 cm) to the left-hand side of the module in order
to allow a free airflow for the temperature sensor and
accessibility of the setpoint dial.
Do not mount the wall modules on an outside wall,
on a wall containing water pipes, or near air ducts.
Avoid locations that are exposed to discharge air
from registers or radiation from lights, appliances, or
the sun.
The T7460D,E,F should not be connected to con-
trollers that do not support fan operation (i.e., the
W7751, W7762, W7763, W7704, and XFC2xxxx /
XFC3xxxx).
When used with CPO-FB22344R-xxx controllers,
either setpoint override or fan-speed adjustment is
supported.
Keep wiring at least 1 ft (305 mm) away from large
inductive loads such as motors, line starters, lighting
ballasts, and large power distribution panels. Run
wall module wiring separately from 50 Vac or greater
power wiring.
2-3/8
(60)
2-11/16
(68)
Fig. 2. Bore-holes for T7460 wall modules in in. (mm)
same for all six models.
WALL MODULES
JUMPER
A
B
1:W7750
W7751
W7752
W7762
2:W7753
3:XL500
3-7/16
(86)
BORE-HOLE DIMENSIONS
FOR OPTIONAL WALL
MOUNTING
EN1B-0291GE51 R0718B

Advertisement

loading

Summary of Contents for Honeywell T7460B

  • Page 1 Fig. 2. Bore-holes for T7460 wall modules in in. (mm) INSTALLATION See Fig. 3 for mounting dimensions. The T7460B,C,D,E,F packages include two setpoint dials. By NOTE: Graphics depict E/F model. Dimensions are the default, the “Celsius Relative” type is mounted. This can be same for all six models.
  • Page 2: Mounting Procedure

    4. Connect the wires to the terminal block according to the specifications in section “Wiring”. 5. (T7460B,C,D,E,F only) With the double-D hole of the potentiometer in the "12 o'clock" orientation (see Fig. 4), hold the setpoint dial such that the "21" (Celsius absolute scale) or "0"...
  • Page 3: Jumper Settings

    T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS Table 2. Wiring terminal references for non-Excel 10/12 devices signal T7460A T7460B T7460C Excel 800 Excel 500 Excel 500 Excel 100 Excel 50 Excel 20 CPO- Smart I/O terminal terminal terminal XF82x term. XF52xB term.
  • Page 4 THE WHITE / UNSHADED TERMINALS ARE NOT INTERNALLY CONNECTED. Wiring of Modules: TERMINAL 1 2 3 T7460A BLOCK SETPOINT (T7460B, only) 1 2 3 T7460B Fig. 7. Wiring diagram for T7460A,B Wall Modules FAN SWITCH BYPASS BUTTON (T7460D,E,F only) (T7460C,E,F only) (T7460C,E,F only)
  • Page 5 T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS SENSOR T7460A,B SET PT Fig. 9. Circuitry of T7460A,B Wall Modules T7460C,D,E,F T7460C,D,E,F JUMPER B IN JUMPER A IN SENSOR POS. 1 OR POS. 2 POS. 1 T7460C,D,E,F SET PT Auto T7460D,E,F BYP/FAN 10 kOhm ONLY A IN POS.
  • Page 6 T7460A,B,C,D,E,F WALL MODULES – INSTALLATION INSTRUCTIONS Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Home and Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany...