3.6 COMMUNICATION

3. 6. 1 Port 1 configuration

The TR80 wall module is a Modbus slave on its port 1.
Register
type
Holding
Holding
Holding
Holding

3. 6. 2 Port 2 configuration

Port 2 on the TR80 wall module has two functions. It can act as a repeater between a master
controller and a downstream DALI64 sensor. Secondly, it can send basic light level and scene
commands of the user directly to a DALI64MOD sensor. These two functions do not conflict,
they can be used simultaneously.
Register
type
Holding
Holding
Holding
Holding
Holding
*
Baud rate and parity enumerations are same as
33
Relative
Absolute
Dir
Address
Address
2002
42003
R/W
2003
42004
R/W
2004
42005
R/W
2005
42006
R/W
Relative
Absolute
Dir
Address
Address
2006
42007
R/W
2007
42008
R/W
2008
42009
R/W
2009
42010
R/W
2010
42011
R/W
Config
Name
parameter
Modbus
slave
4
address
Port 1 baud
5
rate
Port 1 parity
6
Port 1
number of
7
stop bits
Config
Name
parameter
Port 2 baud
8
rate
Port 2 parity
9
Port 2 number
10
of stop bits
Port 2
Response
11
Timeout
DALI64 slave
12
address
Port 1
configuration.
TR80 - Installation and Operation Guide
Type
Range
int
1-247
0: 1200 baud
1: 2400 baud
2: 4800 baud
enum
3: 9600 baud
4: 14400 baud
5: 19200 baud
6: 38400 baud
0: none
enum
1: odd
2: even
int
1-2
Type /
Range
Unit
*
enum
See port 1
*
enum
See port 1
int
1-2
msec
200-3000
0-247
int
(0=disable
d)
Default
value
2
5
2
1
Default
value
5
2
1
500
1