Installation
3.8.6 Auxiliary Power Configuration
Flexput circuits 1-6 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are as follows:
Door Holder
Constant
Resettable

Sounder Sync Power

Auxiliary power must be wired in Class A configuration per UL864 10th Edition. Auxiliary power circuits are power-limited. Each circuit
provides up to 3A (total current for all Flexput circuits must not exceed 5A).
To configure a Flexput circuit as auxiliary power:
1.
Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 2.1 for location of Flexput circuits. When used as auxiliary
power, terminals labeled "0" are negative and terminals labeled "X" are positive.
2.
Configure the auxiliary power output through programming for Door Holder, Constant or Resettable power.

Door Holder Power

The door holder is intended for fire door applications. When there are no alarms in the system and the panel has AC power, the door holder
circuits have 24VDC power present at their terminals. Any alarm will cause power to discontinue. When the system is reset, the power will
be reapplied. If the AC power is off for more than 15 seconds, the auxiliary door holder power will be discontinued to conserve the battery
backup power. When the AC power is restored, the power is immediately restored to the door holder circuits.

Constant Power

Use the constant power for applications that require a constant auxiliary power source. The power is always present at constant circuits.

Resettable Power

The resettable power is typically used to power the beam detectors, flame detectors, and conventional 4-wire smoke detectors. For circuits
selected as Resettable, 24VDC power is always present at the terminals unless a system reset occurs. If a system reset occurs, the power is
removed from the terminals for 30 seconds, then the power is reapplied.
Sounder Sync Power
The Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with the B200S Series
sounder bases.

3.9 Conventional Relay Installation

RPS-1000 relay circuits are installed in exactly the same way as the FACP main panel relay circuits. For ease of installation, RPS-1000 out-
put terminals use the same numbering scheme as FACP terminals. For information on installing the conventional relays, refer to the FACP