3. Modbus with override from button: In this case, the master controller determines the
occupancy mode based on a time schedule, presence detector and/or other inputs.
However, the user may be allowed to override the current mode using the occupancy
button.This allows user to select further modes such as holiday or bypass.
Register
type
Holding

3. 13. 2 Occupancy control

The master controller should read the user selected occupancy mode from the 'Effective Occu-
pancy Mode' register. This is the register that reflects the current effective mode and that is
used for display on the wall module.
Unless the very simple, button-only selection mode is being used, the master controller should
also write its calculated occupancy mode to the 'master occupancy mode' register. This is nec-
essary for display, override functionality and to determine which overrides are allowed. It would
typically be occupied, unoccupied, standby or off.
Register
type
Holding
Holding
Input
Input
47
Relative
Absolute
Dir
Address
Address
2500
42501
R/W
Relative
Absolute
Address
Address
1500
41501
1501
41502
500
30501
501
30502
Config
Name
parameter
Occupancy
500
Source
Dir
Name
Master
R/W
Occupancy Mode
User Occupancy
R/W
Mode
Effective
R
Occupancy Mode
Occupancy
R
Override Status
TR80 - Installation and Operation Guide
Type
Range
0: Modbus only
1: Button only
enum
2: Modbus &
override from
button
Type
Range
0: unknown
1: not used
2: occupied
3: off
enum
4: holiday
5: unoccupied
6: standby
7: bypass
0: auto
1: not used
2: occupied
3: off
enum
4: holiday
5: unoccupied
6: standby
7: bypass
0: unknown
1: not used
2: occupied
3: off
enum
4: holiday
5: unoccupied
6: standby
7: bypass
0: not overriden
enum
1: overriden
Default
value
0
Default
value
0
0
0
0