the machine must be transported according to the regulations in force taking into account the characteristics of the fluids in the machine and the description of these
on the safety data sheet
inappropriate transport can cause damage to the machine and even leaking of the cooling fluid. Before start-up, the machine must be checked for leaks and repaired
accordingly
the accidental discharge of refrigerant in a closed area can cause a lack of oxygen and, therefore, the risk of asphyxiation: install the machinery in a well ventilated
environment according to EN 378-3 and the local regulations in force
the installation must comply with the requirements of EN 378-3 and the local regulations in force; in the case of installations indoors, good ventilation must be
guaranteed and refrigerant detectors must be fitted when necessary.
unless arranged otherwise with MEHITS, the machine be installed in environments where there is no risk of explosion (SAFE AREA)
the structure of the unit is not designed to withstand the stresses (accelerations) caused by an earthquake
before initial start-up, and in any case before maintenance, check that any shut-off taps of the cooling circuit are fully open
Residual risks
Residual mechanical risks
Residual electrical risks
Other residual risks
Residual risks for maintenance
3.5
General precautions
during storage and transport, keep the machine within the following temperature ranges in relation to the refrigerant inside (wider ranges are possible and must be
requested when ordering):
T min (°C)
T max (°C)
prevent the fluids in contact with the heat exchangers from exceeding the limits prescribed in the technical bulletin or from freezing, even when the unit is turned off
when there is a hydraulic circuit, do not use fluids other than water or mixtures of water and ethylene/propylene glycol at the maximum concentration allowed for the
components installed
the machine must only be put to the use for which it was designed; any other uses can be dangerous and will render the guarantee null and void
carrying out maintenance on the product can be dangerous: in the event of a fault or malfunctioning, please contact an authorised assistance centre
the installation must guarantee that the temperature of the fluid entering the unit remains stable and within the range indicated; be careful, therefore, when adjusting
any external heat exchanging and control equipment (dry coolers, cooling towers, zone valves, etc.), sizing the mass of fluid circulating the plant (particularly when
parts of the plant are excluded) and installing systems for circulating the required amount of fluid, in order to keep the temperature of the machine within the allowable
ranges (e.g. during start-up).
the packaging used to protect the machine must always be kept out of the reach of children as it represents a hazard
in units with compressors in parallel, do not disable the individual compressors for long periods of time; always respect the demand limit function
If necessary, use the emergency circuit breaker to disconnect the unit from the power supply
3.6
Environmental information
The cooling circuit contains fluorinated greenhouse gas covered by the Kyoto Protocol. The units may only be serviced and disposed of by qualified technicians.
The fluorinated greenhouse gases contained in the cooling circuit must not be disposed of in the atmosphere.
R134a
GWP
ITH (IPCC
100yr
1430
AR4)
GWP
ITH (IPCC
100yr
1300
AR5)
MITSUBISHI ELECTRIC HYDRONICS & IT COOLING SYSTEM S.p.A.
R134a / R1234ze / R1234yf / R513A
-10
55
R1234ze
R1234yf
R513A
7
4
631
<1
<1
573
Mandatory personal protective equipment
R410A
R404A
2088
3922
1920
3940
Translation of the original instructions
29
EN
R410A / R404A / R407C / R454B / R32
-10
45
R407C
R454B
1774
466
1620
467
Tab.1
R32
675
677
Tab.2