Temperature Sensors; Activation And Adjustment Of Temperature Sensors; Setting The Temperature Switching Values - Bartec APEXmpc Operating Instruction And Safety Manual

Manual ex p control unit
Table of Contents

Advertisement

Ex p control unit
Motor purge controller

7.17 Temperature sensors

Activation and adjustment of temperature sensors

Setting the temperature switching values

Rev. 0
Procedure:
Connect the PC with the Ex p control unit
Activate the programming switch
Log in with the user level
Call up the menu page "Extended / Sensors" in the WEB interface
Activate the desired temperature sensor by clicking on "PT 100 / PT 1000"
e.g. when using three PT100 sensors:
Temperature sensor 1 to 3 on PT 100
Activate the desired display unit "° C / ° F" by clicking on it
Display unit is set on ° C
Procedure:
Call up the menu page "Temperature sensors" in the WEB interface
When activated, the indicator light for temperature sensor x shows that this
sensor is active.
Store temperature switching values 1, 2 and 3
e.g. T. switching value 1 = 35 ° C; T. switching value 2 = 45 ° C; T. switching value
3 = 60 ° C
Store functions for switching values
e.g. function switching value 1 = open valve 1, switching value 2 = warning
message; Switching value 3 = deactivation of Ex p + alarm message
If switching value 1 is exceeded, the purging gas valve is opened for cooling; if
switching value 2 is exceeded, a plain text message is sent in the web interface;
if the value continues to rise to 3, the Ex p system is deactivated
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Operation
The temperature sensors are configured in the
"Extended / Sensors" menu.
The temperature switching values for temperature
sensors 1 to 3 are configured in the "Temperature
sensors" menu.
Page 63 of 96