Technical data

11.2 Ex p control unit SILASmpc

Parameter
Type
EU type examination certificate
IECEx certification
EAC certification
ATEX Marking
IECEx Marking
EAC Marking
Operating ambient temperature
Storage and transport
Material
Mains Voltage DC (Variant)
Mains Voltage AC (Variant)
Current consumption control unit
Maximum power consumption
Release relay K1 (SIL)
Release relay K2 (SIL)
Signal relay K3 and K4
Pressure range
Tolerance range
Purge volume
Purge time
Purge gas valve
Connecting terminal "Ex e"
With wire end ferrule
with plastic collar
Connecting terminal "Ex i"
With wire end ferrule
with plastic collar
Dimensions
Assembly
Cable entry
Ingress Protection (IP) Rating
Purge gas feed – mpc
Purge gas supply – motor
Pressure measurement connections
Weight
Page 84 of 96
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Technical details
A7-37S2-2111/.M5.
BVS 19 ATEX E 016 X
IECEx BVS 19.0038X
ЕАЭС RU С-DE.АЖ58.В.01809/21
II 3G Ex ec mc ic [ic pzc] IIC T4 Gc
II 3D Ex tc [ic pzc] IIIC T130 °C Dc
Ex ec mc ic [ic pzc] IIC T4 Gc
Ex tc [ic pzc] IIIC T130 °C Dc
2Ex ic e mc [ic pz] [ia Ga] IIC T5 Gc X
2Ex ic e mc [ic pz] [ia Ga] IIC T4 Gb X
Ex tc [ic pz] IIIC T95 °C Dc X
Ex tc [ib pz] IIIC T130 °C Dc X
-25 °C tos +50 °C,
-50 °C to +50 °C (variant)
-25 °C to +60 °C @ T4
Stainless steel V4A
24 V dc to 44 V dc
100 V ac to 230 V ac
2 A
25 W (incl. purge valve)
2 potential-related NO contacts,
230 V ac @ 5 A (AC1) or
24 V dc @ 5 A (DC1)
Potential-free, 4 x NO,
230 V ac @ 3 A, 24 V dc @ 3 A
Potential-free, 1x changeover contact,
230 V ac @ 1 A, 24 V dc @ 1 A
0 ... 25 mbar
±0,4 mbar
0 ... 500 m³/h with mpv 3
0 ... 200 m³/h with mpv 2
Up to max. 2 hours
Digital (purging) and proportional (leakage compensation)
0.08 ... 2.5 mm² (28 ...12 AWG)
0.25 ... 1,5 mm²
0.2 ... 2.0 mm² (20 ...14 AWG)
0.25 ... 0.75 mm²
550W x 400H x 250D mm
External
3 x M20, 2x M25
IP 64 in accordance with IEC/EN 60079-0
IP 66 in accordance with EN/IEC 60529
G ½" (i)
G 1 ½" (a)
3x tubes 10 mm
40 kg
Ex p control unit
Motor Purge Controller
Rev. 0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silasmpc07-37a2-2211/m5A7-37s2-2111/m5

Table of Contents