Safety Function; Safety Parameters - Bartec APEXpy 07-37A2-2111/ 520Series Operating Instructions Manual

Ex p control unit
Table of Contents

Advertisement

Ex p Control unit
APEX
py

Safety function

Safety parameters

Rev. 0
The safety function of the Ex p control unit is the purging with a defined quantity
of purging gas, the safe monitoring of the internal overpressure of the protected
equipment and the release for operation. The safe state means that in the event
of a drop in pressure or malfunction, the Ex p control unit switches to the safe
state = deactivation of the protected equipment.
The "safe state" is triggered by:
Falling below the minimum pressures within the Ex p equipment
Illogical pressure values within the Ex p equipment
Failure of the supply voltage
If the Ex p control unit does not deactivate or does not change to the safe state
on request or in the case of an error, a hazardous failure exists.
THE FOLLOWING SAFETY PARAMETERS ARE WITHOUT OPTIONAL
SENSORS.
The optional sensors must be considered to determine the total
failure rate!
 The safety parameters may be derived from the
documentation on the optional sensors used.
Safety parameters according to IEC/EN 61508 / DIN EN ISO 13849-:
SIL = 2
Performance Level: = d
PFH
= (PFH_S+_PFH_L+PFH_FE+PFH_C) = 1.70E-08
sys
HFT = 1
SFF
= 92.85 %
sys
MTTFd = 76 Yr
DC = 88.78 %
Device type B (complex equipment)
Interval of retests = 1 year
Category 3
01-37A2-7D0006_py_Manual_Exp-Control-Unit_20210923_a_en.docx
Safety
Page 17 of 96