Connection Terminals "Ex I - Bartec APEXmpc Operating Instruction And Safety Manual

Manual ex p control unit
Table of Contents

Advertisement

Ex p control unit
Motor purge controller

Connection terminals "Ex i"

6.2.2.1 Terminal row "X9"
Rev. 0
DANGER
DEATH OR SERIOUS PERSONAL INJURY DUE TO OPERATION WITH BYPASS
KEY SWITCH IN EXPLOSIVE ATMOSPHERE.
Risk of explosion.
 Have the start-up with the bypass key switch approved by the
operations manager or his representative. Approval may only be
granted if it is ensured that there is no explosive atmosphere for the
period of start-up, or, where necessary, protective measures against
the risk of explosion have been taken (fire permit).
 A label on the bypass key switch stating that the explosion protection
is deactivated when the key switch is activated must be attached in
the direct area of the key switch.
A bypass key switch can be connected separately to the APEX / SILAS control
unit.
The bypass key switch must be labelled according to the label below and must
be attached in the immediate vicinity of the bypass key switch.
The position of the bypass key switch is queried by the control electronics in an
intrinsically safe manner.
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Electrical connections
Page 41 of 96