Installing The Chassis In A Rack; Rack-Mounting The Chassis - Alcatel-Lucent 7705 Installation Manual

Service aggregation router
Hide thumbs Also See for 7705:
Table of Contents

Advertisement

Installing the Chassis

Installing the Chassis in a Rack

Danger: Only trained and qualified personnel should install or replace this equipment.
Warnings:

Rack-Mounting the Chassis

The 7705 SAR-F chassis is designed for installation in a 19-inch rack. The rack-mount
brackets are factory-installed.
Page 62
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to
a nearby ground point that is connected to the site grounding point when working on the
7705 SAR-F. Typical ground points include the ground connection point on the front of
the 7705 SAR-F, the grounding stud on the 7705 SAR-F mounting bracket, or a properly
grounded rack or work bench.
Failure to comply with the location requirements outlined in
52
Chassis Location Requirements on page 52
and
result in thermal failure.
Non-conductive coatings (such as lacquer and enamel) must be removed from threads
and other contact surfaces to ensure electrical conductivity. Thread-forming screws with
paint piercing washers may be used for this purpose during installation.
When rack-mounting the chassis in an equipment rack, do not stack one 7705 SAR-F
chassis or any other equipment directly on top of another 7705 SAR-F chassis, such that
the bottom chassis is supporting other devices. Each chassis must be secured in the rack
with the appropriate mounting apparatus.
Figure 10
illustrates the installation of the chassis in a rack.
7705 SAR-F Installation Guide
Installation Locations on page
will impede proper airflow and will