Reference Value - Omron S82K Series Manual

Switching power supply
Hide thumbs Also See for S82K Series:
Table of Contents

Advertisement

New S82K
90-/100-/240-W models with PFC (S82K-Pjjj24 models)
Item
Other
Ambient temperature
Ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Screw tightening
torque
Output indicator
Electromagnetic
interference
(see note 1)
EMC (see note 3, 4)
Approved standards
Weight
Note:
1. Defined with a 100% load and the rated input voltage (100 or 200 VAC)
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. To ensure the Emission Enclosure ratings, a noise filter should be used on the output lines at the closest point. (90- and 100-W
models: S82Y-JF6-N)
4. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables.
5. To meet Class-2 requirements with the 100-W model, either a fuse or circuit breaker that is UL listed or CSA certified, and rated at
4.2 A max. should be wired in series with the load to be connected to the power supply. Only then can the power supply output be
considered as meeting Class 2.

Reference Value

Item
135,000 hrs min.
Reliability (MTBF)
Life expectancy
8 yrs. min.
10
90 W
Operating: See the derating curve in the Engineering Data section (No condensation or icing)
Storage:
- -25"C to 65"C (no condensation or icing)
Operating: 25% to 85%
Storage:
25% to 90%
3,000 VAC at 50/60 Hz for 1 min. (between all inputs and outputs)
2,000 VAC at 50/60 Hz for 1 min. (between all inputs and GR terminal)
1,000 VAC at 50/60 Hz for 1 min. (between all outputs and GR terminal)
Alarm current: 20 mA (90- and 100-W models) 25 mA (240-W models)
100 M# min. at 500 VDC (between all outputs and all inputs/GR terminal)
Malfunction: 10 to 55 Hz, 0.375-mm single amplitude for
2 hrs each in X, Y, and Z directions
2
, 3 times each in !X, !Y, and !Z
Malfunction: 150 m/s
directions
0.74 N S m max. (see note 2)
Yes (Green)
Conforms to FCC class A
90-, 100-W Models
(EMI):
EN50081-1
Harmonic Current:
EN61000-3-2 (200 VAC input only)
Emission Enclosure:
EN55022 class B
Emission AC Mains:
EN55022 class B
Emission Output Ports: EN55022 class A (with a recommended optional filter) (see note 3)
240-W Model
(EMI):
EN50081-2
Harmonic Current:
EN61000-3-2
Emission Enclosure:
EN55011 class A (see note 4)
Emission AC Mains:
EN55011 class A
Common to All Models
(EMS):
EN50082-2
Immunity ESD:
EN61000-4-2:
Immunity Burst:
EN61000-4-4:
Immunity Surge:
EN61000-4-5:
Class 2 (UL1310)/Class 2 (CSA C22.2 No. 950) (see
note 5)
UL508 (Listing)/1950
CSA C22.2 No. 14/No. 950, EN50178 (VDE160),
EN60950
Conforms to VDE0106/P100
1,000 g max.
Value
MTBF stands for Mean Time Between Failures, which is calculated according to the
probability of accidental device failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
The life expectancy indicates average operating hours under the ambient
temperature of 40"C and a load rate of 50%. Normally this is determined by the life
expectancy of the built-in aluminum electrolytic capacitor.
Single output
100 W
Malfunction: 10 to 55 Hz, 0.15-mm
Malfunction: 300 m/s
4-kV contact discharge (level 2)
8-kV air discharge (level 3)
2-kV power-line (level 3)
2-kV output line (level 4)
between 2-kV lines (except for 240-W models)
between 4-kV line and FG (except for 240-W models)
UL508 (Listing)/1012
CSA C22.2 No. 14/E.B. 1402C,
EN50178 (VDE160), EN60950,
Conforms to VDE0106/P100
2,200 g max.
Definition
New S82K
240 W
single amplitude for 2 hrs
each in X, Y, and Z
directions
2
, 3 times each in
!X, !Y, and !Z directions