Reference Value - Omron S8VK-G Series Manual

Switch mode power supply
Hide thumbs Also See for S8VK-G Series:
Table of Contents

Advertisement

Two phases application for Single phase models
For All Single phase Models, S8VK-G
Basically OMRON single phase power supply can be used on two-
phases of a 3–phase-system when some of conditions satisfy like
below.
1. The supplying voltage is below the maximum rated input.
OMRON Power supply allows the input voltage equivalent or less
than 240 VAC+10%.
Please confirm the input voltage between two lines if the input
voltage satisfies this condition before connecting.
2. The external protector is needed on N input line to secure a safety.
N line has no protection of a fuse internally.
An appropriate fuse or circuit breaker should be connected on N
input line like the following.
L
L
L
PE
1
2
3
An external
fuse or a
circuit breaker

Reference Value

Value
Single phase model
15 W: 600,000 hrs
Reliability
30 W: 580,000 hrs
(MTBF)
60 W: 590,000 hrs
120 W: 450,000 hrs
240 W: 360,000 hrs
480 W: 230,000 hrs
MTBF stands for Mean Time Between
Failures, which is calculated according to the
probability of accidental device failures, and
Definition
indicates reliability of devices.
Therefore, it does not necessarily represent a
life of the product.
Life expectancy
10 yrs. Min.
The life expectancy indicates average
operating hours under the ambient
temperature of 40°C and a load rate of 50%.
Definition
Normally this is determined by the life
expectancy of the built-in aluminum electrolytic
capacitor.
Power Supply
Internal
Fuse
L
N
max. 240 VAC+10%
S8VK-G
11