Switching Power Supply
Ultimate DIN-track-mounting Power
Supply with a Wide Power Range from
3 to 240 W
Wide power range: 3 to 240 W
Wide AC input voltage range: 100 to 240 V on one
body.
Undervoltage alarm function (indicator) incorpo-
rated as standard. (With the 240-W models,
applicable only to the "-T" models.) 90 and 100-W
models standardized with the alarm output.
Output/input terminal parts separated on body
upper/bottom side, respectively, for safe and smart
wiring.
Multiple pairs of output terminals;
Three pairs for 90, 100, and 240-W models
Two pairs for 30 and 50-W models
Finger-safe terminal block with cover according to
VDE0106/P100.
Conforms to the stringent EN50081-1 standard for
universal use in any environment subject to EMI
conditions (except for 240-W models) in addition to
EN50082-2 conformity for use at any EMS
environment.
DC output ports comply to EN55022 class A, thus
ensuring use in any environment subject to EMI
with recommended external filters (3- to 100-W
models).
Meets EN61000-3-2 (limits for harmonic current
emissions) with PFC on 90, 100, and 240-W
models.
Parallel running operation (100 and 240-W
models).
Class 2 approved (except for 240-W models and
7.5-W dual output models).
Approvals of various international safety standards
for industrial control equipment and industrial
computing systems (ITE/TE), in addition to other
important approvals.
Six-language instruction manual provided.
4
New S82K
RuCW

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S82K Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Omron S82K Series

  • Page 1 Switching Power Supply New S82K Ultimate DIN-track-mounting Power Supply with a Wide Power Range from 3 to 240 W Wide power range: 3 to 240 W Wide AC input voltage range: 100 to 240 V on one body. Undervoltage alarm function (indicator) incorpo- rated as standard.
  • Page 2: Ordering Information

    New S82K New S82K Ordering Information 3 to 240-W Models Power ratings Output voltage Output current Function Configuration Models Output Undervoltage alarm indicator/output 0.6 A Single output S82K-00305 12 V 0.25 A S82K-00312 15 V 0.2 A S82K-00315 24 V 0.13 A S82K-00324 7.5 W...
  • Page 3: Specifications

    New S82K New S82K Specifications Ratings/Characteristics 3- to 240-W models without PFC Single output Dual Single output Item outputs 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W Efficiency (typical) 60% to 80% (Varies depending on specifications.) Input Voltage 100 to 240 V (85 to 264 V)
  • Page 4 New S82K New S82K 3- to 240-W models without PFC Single output Dual Single output Item outputs 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W !10% (V.ADJ) !10% (V.ADJ); - -10% to 15% for S82K-03012/-03024/-05024 Output Voltage adjustment Not pos-...
  • Page 5 New S82K New S82K 3- to 240-W models without PFC Single output Dual Single output Item outputs 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W Other Ambient Operating: See the derating curve in the Engineering Data section temperature (no condensation or icing) Storage:...
  • Page 6 New S82K New S82K 90-/100-/240-W models with PFC (S82K-Pjjj24 models) Single output Item 90 W 100 W 240 W 60% to 80% (Varies depending on specifications.) Efficiency (typical) Input Voltage 100 V (85 to 132 VAC)/200 V (170 to 264 VAC) 100 to 230 V (85 to 253 VAC) Selectable Frequency...
  • Page 7: Reference Value

    New S82K New S82K 90-/100-/240-W models with PFC (S82K-Pjjj24 models) Single output Item 90 W 100 W 240 W Other Operating: See the derating curve in the Engineering Data section (No condensation or icing) Ambient temperature Storage: - -25"C to 65"C (no condensation or icing) Ambient humidity Operating: 25% to 85% Storage:...
  • Page 8: Engineering Data

    New S82K New S82K Engineering Data Derating Curve 3-/7.5-/15-/30-/50-/100-W Models 100-W Models without PFC 100-W Models with PFC Single-Unit Operation Parallel-Unit Operation Parallel-Unit Operation Installation A Installation A Installation B Installation A S82K-P10024: 85-VAC input S82K-P10024: 85-VAC input Installation B S82K-03005 Installation B Installation A...
  • Page 9: Overload Protection

    New S82K New S82K Overload Protection The Power Supply is provided with an overload protection function that protects the load and the power supply from possible damage by over- current. When the output current rises above a set value (refer to the table below), the protection function is triggered, decreasing the output voltage.
  • Page 10 New S82K New S82K Overvoltage Protection (S82K-24024T Models Only) The Power Supply is provided with an overvoltage protection function that protects the load and the Power Supply from possible damage by overvoltage. When the output voltage rises above a set value, the protection function is triggered, shutting off the output voltage. If this occurs, reset the Power Supply by turning it off for 1 minute min.
  • Page 11: Operation

    New S82K New S82K Operation Undervoltage Alarm Indicator and Output Function (All Models Except for S82K-24024/P24024) If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the S82K (DC LOW indicator) will be lit. In the case of the S82K-j09024/j10024/24024T, a voltage drop alarm will be output via the relay available in the models (DC LOW output).
  • Page 12 New S82K New S82K S82K-015jj (15 W) S82K-030jj (30 W) S82K-05024 (50 W) Fuse (3 A) AC (L) Noise filter - - V AC (N) Inrush current Rectifier Rectifier protection circuit Undervoltage Drive control alarm circuit indicator Overload Detector alarm circuit Photocoupler S82K-09024 (90 W)
  • Page 13 New S82K New S82K S82K-24024j (240 W) Fuse (5 A) AC (L) INPUT Noise filter AC (N) Inrush current Rectifier protection circuit 100 or 200 V OUTPUT Selectable - - V terminals Rectifier (see note 2) Drive control circuit Detector DC LOW Photocoupler Undervoltage...
  • Page 14 New S82K New S82K Dimensions Note: All units are in millimeters unless otherwise indicated. S82K-003jj (3 W) Mounting Brackets S82K-007jj (7.5 W) (Supplied with the Switching Power Supply) Used when not mounting the Power Supply directly on the DIN track. Two, 4.5! dia.
  • Page 15 New S82K New S82K S82K-030jj (30 W) S82K-05024 (50 W) Four, 4.5 dia. M3.5 with square washer (sliding 7 max.) Mounting Holes Four, M4 or 4.5-dia. mounting holes If more than one Power Supply is Note: installed in a row, keep a distance of 20 mm min.
  • Page 16 New S82K New S82K S82K-j24024j 270!0.2 Four, 4.5 dia. 27.5 112.8 115!0.2 M3.5 terminal screw 4 (sliding 8 max.) M3.5 with square washer Short bar Mounting Holes 115!0.2 Four, M4 or 4.5-dia. mounting holes Note: If more than one Power Supply is installed in a row, keep a distance of 20 mm min.
  • Page 17: Installation

    New S82K New S82K Installation S82K-003jj/S82K-007jj S82K-007jj (Dual outputs) S82K-015jj (Single Output) S82K-j09024/S82K-j10024 S82K-030jj/S82K-05024 Bottom view 6 7 5 S82K-j24024j (Only for S82K-P10024) Bottom view 1. DC Output Terminals: Connect the load lines to these terminals. 2. Input Terminals: Connect the input lines to these terminals. 3.
  • Page 18 New S82K New S82K Precautions Caution To dismount the Power Supply, pull down portion (C) with a flat- blade screwdriver and pull out the Power Supply. Be sure to connect the grounding line. Not doing so may result in electric shock. WARNING Do not attempt to disassemble the Power Supply or touch its internal parts while power is being supplied.
  • Page 19 New S82K New S82K Wiring Parallel Operation Carefully wire the input/output terminals while paying attention to S82K 100-W/240-W models can be operated in parallel. their polarities so as to prevent incorrect wiring. Perform parallel operation with power supplies satisfying the same specifications.
  • Page 20 New S82K New S82K Minimum Output Current The minimum output current of the S82K-00727 and S82K-00728 is restricted by the output voltage and control method. Note: All the outputs of the S82K-00727 and S82K-00728 are controlled by the +V output. If the +V output current falls to 10% or less of the rated output, the - -V output voltage may drop.
  • Page 21 To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. M048-E1-5 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company Measuring and Supervisory Controls Department 28th Fl., Crystal Tower Bldg.,...

Table of Contents

Save PDF