Switch mode power supply ethernet/ip, modbus tcp-compatible maximizing system availability through the connecting of equipment to iot (38 pages)
Summary of Contents for Omron S82K
Page 1
Switching Power Supply S82K DIN-Rail Mount Power Supply with a Wide Power Range of 3 to 240 W Universal voltage range: 100 to 240 VAC UL 508 listed on all models Class 2 approved on all models below 240-W, except dual-output types Undervoltage indicators on all.
Page 2
24 V 10 A With PFC S82K-P24024 J MODEL NUMBER LEGEND 3- to 100-W Models 1. Power Ratings 2. Output Voltage S82K - 003: 3 W 5 VDC 007: 7.5 W 12 VDC 015: 15 W 15 VDC 030: 30 W...
S82K S82K Specifications J RATINGS/CHARACTERISTICS Non–PFC models PFC model Item Single output Dual Single output outputs 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W 240 W Efficiency (typical) 60% to 80% (Varies depending on specifications.)
Page 4
15 W 30 W 50 W 90 W 100 W 240 W 240 W Output Voltage adjust- 10% (V.ADJ) 10% (V.ADJ); –10% to 15% for S82K-03012/-03024/-05024 (see ment range pos- note 2) sible (see note 3) Output Ripple 2% (p-p) max.
Page 5
S82K S82K Specifications Table – continued from previous page Item Non–PFC models PFC model Single output Dual Single output outputs 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W 240 W Addi- Overload...
Page 6
(3- to 50-W models: S82Y-JF3-N, 90- and 100-W models: S82Y-JF6-N) 4. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables (for S82K-P24024). 5. Models other than dual output models satisfy the Class-2 requirements.
S82K S82K J REFERENCE VALUE Item Value Definition Reliability (MTBF) 135,000 hrs min. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent a life of the product.
Page 8
Note: To avoid damage to the unit or deterioration of the internal voltage Variable range circuitry, do not short-circuit the output terminals of the –10% S82K or use the S82K with excessive output current for a long time. 3-/7.5-/15-/90-W/100-/240-W Models Rated voltage Output current (%)
(ALL MODELS EXCEPT S82K-24024/P24024) If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the S82K (DC LOW indicator) will be lit. In the case of the S82K-10024/24024T, a voltage drop alarm will be output via the relay available in the models (DC LOW output).
Page 10
S82K S82K J BLOCK DIAGRAMS S82K-003jj (3 W) S82K-007jj (7.5 W, Single Output) Fuse (1 A) AC (L) Noise filter AC (N) – V Inrush current Rectifier Rectifier protection circuit Undervoltage Drive control alarm circuit indicator Overload Detector alarm circuit Photocoupler S82K-007jj (7.5 W, Dual Outputs)
Page 11
Overvoltage protection circuitry (see note 1) Note: 1. The overvoltage protection circuitry is available in the S82K-24024T only. 2. Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and remove the short bar to select 200 to 230 VAC.
Page 12
S82K S82K Dimensions Unit: mm (inch) J S82K-003jj (3 W) S82K-007jj (7.5 W) 37.5 Mounting Brackets (1.48) (Supplied with the Power Supply) 65 (2.56) Used when not mounting the Power Supply directly on the DIN rail. Two, (2.95) 4.5 dia.
Page 13
S82K S82K Unit: mm (inch) J S82K-030jj (30 W) S82K-05024 (50 W) 90 (3.54) Four, 4.5 dia. 58.1 35.2 (2.95) M3.5 with square washer 91 (3.58) (sliding 7 max.) Mounting Holes Four, M4 or 4.5-dia. mounting holes (2.36) Note: If more than one Power Supply is installed in a row, keep a distance of 20 mm min.
Page 14
S82K S82K J S82K-j24024j 280 (11.02) Four, 4.5 dia. 27.5 112.8 (4.44) (3.94) (5.12) 130 (5.12) Short bar M3.5 M3.5 with square washer terminal (4.53) (sliding 8 screw max.) Mounting Holes L (See Note) 270 (10.63) (4.53) Note: If more than one Power Supply is installed in a row, keep a distance of 20 mm min.
Page 15
S82K S82K J ACCESSORIES Unit: mm (inch) DIN Rail Mounting Track (Order Separately) PFP-100N/PFP-50N PFP-100N2 12, 25 x 4.5 oblong 29.2 25 15 15 (5) 1,000 (500) 1,000 (See Note.) (See Note.) Note: The values shown in parentheses are for the PFP-50N.
5. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON. 6. Output Voltage Adjuster(V.ADJ): It is possible to increase or decrease the output volt- age. 7. Undervoltage Alarm Indicator (DC LOW): All models except S82K-24024 and S82K-P24024. 8. Undervoltage Alarm Output (DC LOW): S82K-09024/S82K-10024/S82K-24024T models only.
Page 17
6. Output Voltage Adjuster(V.ADJ): It is possible to increase or decrease the output voltage. 7. Undervoltage Alarm Indicator (DC LOW): All models except S82K-24024 and S82K-P24024. 8. Undervoltage Alarm Output (DC LOW): S82K-09024/S82K-10024/S82K-24024T models only. 9. Parallel/Single Operation Selector: Set to “PARALLEL” for par-...
Page 18
Power Supply to the rail and press the Power Supply toward shown by the dotted lines in the figure. No diodes are direction (B). required with S82K 90-W/100-W/240-W models. INPUT –V INPUT...
Page 19
INPUT The minimum output current of the S82K-00727 and –V S82K-00728 is restricted by the output voltage and control method. Note: All the outputs of the S82K-00727 and S82K-00728 are controlled by the +V output. If the +V output cur- INPUT rent falls to 10% or less of the rated output, the –V...
Page 20
S82K S82K NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4. OMRON ELECTRONICS, INC. OMRON CANADA, INC. One East Commerce Drive 885 Milner Avenue Schaumburg, IL 60173 Scarborough, Ontario M1B 5V8 1-800-55-OMRON 416-286-6465 Cat. No. M48–E3–3 10/99 Specifications subject to change without notice.
Need help?
Do you have a question about the S82K and is the answer not in the manual?
Questions and answers