72/85
Bosch Rexroth AG
Maintenance and Service
12.2.5
Removing Module from Profile Adapter
12.2.6
Connecting Module
12.3
Disposal
Rexroth IndraControl S67 HTL Encoder/Counter Module 4 Digital Inputs/Outputs (4×M12)
A
Fig. 12-1:
Removing module with mounting rail adapter from mounting rail
If the S67-HTL-INC-M12 module is mounted on a profile adapter, proceed
with the removal as follows:
1. Disconnect the power supply from the device the S67-HTL-INC-M12
module is mounted to before removal.
2. Unscrew the screws the nuts are fastened on and remove the S67-HTL-
INC-M12 module from the profile rail of the system.
3. Unscrew the screws that connect the S67-HTL-INC-M12 module with
the profile adapter.
To connect the new S67-HTL-INC-M12 module, proceed as described in the
following chapters:
●
chapter 5 "Mounting Module" on page 29
●
chapter 6 "Connecting Data and Supply Cables" on page 37
●
chapter 7 "Commissioning" on page 45
Depending on the type of field bus coupler used, the parameters of the previ‐
ous S67-HTL-INC-M12 module are transferred to the new module if necessa‐
ry (see also
chapter 8.9 "Automatic Storage of System Parameters" on page
54).
Do not dispose the IndraControl S67 components with the household waste.
Comply with the regulations. You can also contact a certified waste disposal
company.
DOK-CONTRL-S67HTLM12**-AP02-EN-P