Rs422 Interface - Bartec POLARIS B7-72V1 Series User Manual

Panel pc professional 10.4" / 12.1" / 12.1" w
Hide thumbs Also See for POLARIS B7-72V1 Series:
Table of Contents

Advertisement

POLARIS BASIC
- for Zone 1 / 21
POLARIS Panel PCs 5.7" / 10.4" / 12.1"
Technical data subject to change.
09/2020
Assignment RJ45 plug for Ethernet to POLARIS terminal block
Configuration RS422
Terminal Interface
X17
Termination
X18
On/Off
X19
Interface COM 1
X20
Interface COM 1
X21
Interface COM 1
X22
Interface COM 1
X23
Interface COM 1
X24
Interface COM 1
X25
Interface COM 1
X26
Interface COM 1
Connection PLC with RS422 interface to POLARIS.
Maximum length of the data line 1,000 m.
Connection RJ45
PIN
PIN 1
1
PIN 8
2
3
4
5
6
7
8
Signal
Remarks
Jumper between terminal X17 and
X18 for activation of the terminator
resistors
TxD B (TxD+)
Transmission cable
TxD A (TxD-)
Transmission cableI
RxD B (RxD+)
Receiving cable
RxD A (RxD-)
Receiving cable
TxD B (TxD+)
Transmission cable
TxD A (TxD-)
Transmission cable
RxD B (RxD+)
Receiving cable
RxD A (RxD-)
Receiving cable
Commissioning
POLARIS
Signal
Terminal
TX+
X13
TX-
X14
RX+
X15
not used
not used
RX-
X16
not used
not used
6.6.4

RS422 Interface

Input
Input
Input
Input
Output
Output
Output
Output
EN 31/65