PIPELINE SIZE TABLE TBML 80 PN
PUMP AXIS
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION FEED SYSTEM
PUMP AXIS
Note: For any missing devices in the piping, follow existing regulations.
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
11 / 36
0006081428_201406
6 Suction pipe
7 Return pipe
8 Automatic fuel interception at burner shut off
9 One-way valve
8 Automatic fuel interception device at
burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
1 Tank
3 Wire-net filter
4 Pump
meters
6 Suction pipe
7 Return pipe
0,5
10 Bottom valve
1
1,5
2
2,5
Subtract 0.25 mt. for every bend or gate valve.
Total length
H
meters
meters
Ø i. 14 mm.
1
30
1,5
35
2
35
2,5
40
3
40
Total length
meters
Ø i. 14 mm.
30
35
35
40
40
Dimension P = 3.5 m. (max.)
Total length
meters
H
Ø i. 14
Ø i. 16
mm.
mm.
26
22
19
14
11
45
38
31
25
19