Dry Contact for Alarm Signal
The C1050 has an analog input which can be designated as an alarm signal input. Please refer to Figure 9 to see how to
correctly connect it. To signal an alarm, the contact must be closed. Closing this contact will prevent the use of the com-
pressors, either in heating or cooling. Auxiliary heating will still activate as required.
REV. 7.3.0 / PL-HRDW-HP-C1050-C/F-EN
+
INT
-
24VAC
COM
A
NET
B
DI
UI3
COM
UI2
UI1
Figure 9 - Connecting the Alarm Contact to the Controller
Alarm
11