LEDs

The C1050 has various LEDs which are linked to different functions and outputs of the controller. Each LED is individually
identified to help the user make a quick visual diagnostic of the controller's activity and status.
Green light: Reception from INT port
Red light: Transmission to main bus
Green light: Reception from main bus
Blue pulsing: indicates that
Blue light: Internal 24VDC power source OK

Addressing Dipswitch Configuration for Network Communication

A unique address must be configured on each controller by setting the first 7 switches on the addressing dipswitch to
the desired value.
These switches are numbered from 1 to 7 and represent a binary value from 1 to 64 (1, 2, 4, 8, 16, 32, and 64 respectively).
The last switch (#8) is reserved. The value of each switch that is in the ON position is added together to form the numeri-
cal address of the controller.
The example in Figure 1 shows the switches 1, 2 and 4 in the ON position. Therefore, the corresponding values are 1, 2
and 8, giving an address sum of 11.
The Prolon network allows a maximum of 127 addresses, therefore 127 controllers.
REV. 7.3.0 / PL-HRDW-HP-C1050-C/F-EN
the CPU is online

Figure 2 - LEDs Identification

Figure 3 - Addressing Dipswitches

Red light: Transmission to interface
Reserved
Status light for analog output 5
Status light for triac output 4
Status light for triac output 3
Status light for triac output 2
Status light for triac output 1 (Fan)