Technical Specifications

Supply: 24 VAC ±10%, 50/60 Hz, Class 2
Consumption: 2 VA (Consumption), 32 VA (Input)
Inputs: 4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp /
night setback / proof of fan / alarm)
Digital outputs: 4 triac outputs, 10-30 VAC source or dry contact, 300 mA max (resettable fuse)
Analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication lights (LED): State of each output / Communication / Power / State of microprocessor
Microprocessor: PIC18F6722, 8 bits, 40 MHz, 128KB FLASH memory
Casing: Molded ABS, UL94-HB
Communication (HP): Modbus RTU (RS485) or BACnet MS/TP (RS485), up to 127 nodes
Communication (HPS): Modbus RTU (RS485), up to 127 nodes
Baud rate: 9600, 19200, 38400, 57600, 76800, 115200
Connection: Removable screw-type terminal blocks (16 AWG max)
Dimensions: 6.2" x 5.2" x 2.5" (157 mm x 132 mm x 64 mm)
Weight: 0.85 lbs (0.39 kg)
Environment: -4 to 122 ºF (-20 to 50 ºC) Non-Condensing
Certification: UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
The performance specifications are nominal and conform to acceptable industry standards. Prolon Inc. will not be liable for
damages resulting from misapplication or misuse of its products.
15
REV. 7.3.0 / PL-HRDW-HP-C1050-C/F-EN