Input And Output Identification; Figure 4 - Input And Output Identification - Prolon C1050 Series Hardware Manual

Heatpump controller
Hide thumbs Also See for C1050 Series:
Table of Contents

Advertisement

Input and Output Identification

All the inputs and outputs of the C1050 use pluggable screw type terminal blocks with elevator style clamping, which
make connections easier and more secure. Output functionality will vary depending on the number of compressors in
use (1 or 2 - see below).
The C1050 Heatpump Controller has 2 separate communication ports offering varying functionality based on whether
or it is a heatpump standalone controller (HPS) or not (HP).
+
INT
-
24VAC
COM
A
NET
B
DI
UI3
COM
UI2
UI1
AO
DO4
DO3
DO2
DO1
REV. 7.3.0 / PL-HRDW-HP-C1050-C/F-EN
INT Port: Incoming RS485
network communication
NET Port: Outgoing RS485
network communication
to zones (Modbus)
Output 5 - Preheating /
Output 2 - Compressor 1

Figure 4 - Input and Output Identification

PL-C1050-HP
INT Port: Prolon digital temperature
sensor - OR - Incoming RS485
(Modbus)
network communication (Modbus)
PL-C1050-HPS: Power supply to digital sensor (24 VAC)
NET Port: Prolon digital temperature
Sensor - OR - Incoming RS485
network communication (Modbus)
External dry contact for night setback or proof of fan
Supply temperature sensor (10K thermistor)
Common for all the inputs
Return temperature sensor (10K thermistor)
Outside temp (10K therm), water intake temp (10K therm)
or dry contact for alarm
Aux Heat / Econo
Output 4 - Aux Heat
Output 3 - Rev Valve
Output 1 - Fan (G)
Controller's power source Unit's R&C terminal (24VAC)
1 Compressor
PL-C1050-HPS
Output 5 - Aux Heat
Output 4 - Rev Valve
Output 3 - Compressor 2
Output 2 - Compressor 1
Output 1 - Fan (G)
2 Compressors
8