Xinje XD Series User Manual page 59

Hide thumbs Also See for XD Series:
Table of Contents

Advertisement

Not accept narrow input pulse signal
PLC's input ON/OFF time should be longer than its loop time. If consider input filter's
response delay 10ms, loop time is 10ms,then ON/OFF time needs 20 ms separately. So, up
to 1, 000/(20+20)=25Hz input pulse can't be processed. But, this condition could be improved
when use PLC's special function and applied instructions (such as high speed count, input
interruption, input filter adjustment).
Dual output(Dual coils)action
Input process
X0=ON
X1=OFF
X0
OUT
Y0
OUT
X1
OUT
Output process
Y0=OFF
Y 1=ON
When executing dual output (use dual coil), the after one is act in priority.
Y0
Y1
Y0
58
As shown in the left map, please
consider the case of using the same coil
Y0 at many positions:
E.g. X0=ON, X1=OFF
The first Y0: X0 is ON, its image area is
ON, output Y1 is also ON.
The second Y0: as input X1 is OFF, the
image area is OFF.
So, the actual output is: Y0=OFF,
Y1= ON.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xl seriesXd3Xd5