3 Fixed Software Bugs

Writing Commands to the BWU1821

BWU1821
Effects of this Bug
Affected Revisions
Remedy / Workaround
Bug Fix
14
The BWU1821 is a gateway between AS interface and CANopen of the
Bihl+Wiedemann GmbH. It can be directly connected to the Jetter CAN
system bus.
Commands of a length greater than 4 bytes cannot be transmitted to the
BWU1821. The following functions, for example, are affected by this error:
Reading parameters of AS interface slaves according to profile 7.4
Writing parameters to AS interface slaves according to profile 7.4
Reading input data of AS interface slaves according to profile 7.4
Writing output data to AS interface slaves according to profile 7.4
...
The following revisions are affected by this bug:
OS revision
Hardware revision
Configuration or operating mode
Comment
There is no remedy to be applied to the releases concerned.
Starting from the following revisions this bug has been fixed:
OS revision
Hardware revision
Configuration or operating mode
JX6-SB(-I)
< 2.21.0.00
JC-24x
< 3.26.0.00
JM-D203-JC24x
< 1.13.0.00
not relevant
not relevant
610
JX6-SB(-I)
2.21.0.00
JC-24x
3.26.0.00
JM-D203-JC24x
1.13.0.00
not relevant
not relevant