Restrictions At Using The Can System Bus - Jetter JC-24x Version Update

From v 3.25 to v 3.26
Table of Contents

Advertisement

JC-24x - Version Update from 3.25 to 3.26

Restrictions at Using the CAN System Bus

Restrictions at Using the
CPX-CP Interface
Restrictions at
Connecting Analog I/Os
Restrictions at
Connecting CANopen
Modules
Jetter AG
The usage of the CPX-CP interface at the CPX-FB14 is subject to the
following restrictions:
The required hardware and operating system versions have to be kept to.
The CPX-FB14 supports one CPX-CP interface as a maximum.
In the system bus, the CPX-FB14 occupies up to three I/O module
numbers. These I/O module numbers are not available in other modules.
The number of the analog I/Os at the CPX-FB14 is reduced.
At applying the CPX-CPI interface, the number of the analog inputs and
outputs to be connected is reduced.
If at the CP string 1 or 2 ...
CP / CPI output modules are connected,
CP valve terminals are connected,
CP / CPI input modules are connected,
If at the CP string 3 or 4 ...
CP / CPI output modules are connected,
CP valve terminals are connected,
CP / CPI input modules are connected,
By using the additional I/O module numbers, the maximum number of
CANopen modules that can be connected to the CAN system bus is reduced.
Each additional I/O module number causes the number of CANopen modules
to be reduced by one.
New Features
Then the number of ...
the analog outputs is reduced to 8
the analog outputs is reduced to 8
the analog inputs is reduced to 8
Then the number of ...
the analog outputs is reduced to 4
the analog outputs is reduced to 4
the analog inputs is reduced to 4
9

Advertisement

Table of Contents
loading

Table of Contents