N_Copy_To/From(2) With More Than 64 Registers In Mode 2 - Jetter JC-24x Version Update

From v 3.25 to v 3.26
Table of Contents

Advertisement

JC-24x - Version Update from 3.25 to 3.26

N_COPY_TO/FROM(2) with more than 64 registers in mode 2

Effects of this Bug
Affected Revisions
Remedy / Workaround
Bug Fix
Jetter AG
more than 64 register values are sent to another controller or retrieved from it using
one of the following commands
copy mode 2 (decrement register numbers) is used
the registers on the remote controller are incorrectly addressed.
The following revisions are affected by this bug:
OS revision
Hardware revision
Configuration or operating mode
To send a register block exceeding 64 registers use several commands
N_COPY_TO_FROM(2) with a maximum of 64 registers each.
Starting from the following revisions this bug has been fixed:
OS revision
Hardware revision
Configuration or operating mode
Fixed Software Bugs
If ...
N_COPY_TO
N_COPY_TO2
N_COPY_FROM
N_COPY_FROM2
and ...
then ...
JC-24x
JC-24x STX
JM-D203-JC24x
not applicable
not applicable
JC-24x
JC-24x STX
JM-D203-JC24x
not applicable
not applicable
< 3.26.0.00
< 10.04.0.00
< 1.13.0.00
3.26.0.00
10.04.0.00
1.13.0.00
13