2.5 Expansion card

From version 3.3.0, an I/O expansion card can be used to provide additional
analogue and digital channels, ideal when there is a high number of
compressors and corresponding alarms, or with complex heat recovery
systems that require of numerous temperature sensors in the water and
CO2 circuits (see technical leafl et +0500059IE for the product's electrical
and physical specifi cations). The universal inputs/outputs (marked U on
the connection diagram) can be confi gured by pRack pR300T to connect
active and passive probes, digital inputs, analogue and PWM outputs, up
to a total of 10. A further 6 digital outputs are also available.
8
Address
Ext Baud Prot
4
1
2
3
4
5
6
7
8
ON
OFF
Address
1
Key:
1
Power connector [G(+), G0(-), Vbat]
2
Universal inputs/outputs
3
+Vdc power supply for active probes
4
+5V power supply for ratiometric probes
5
Relay digital outputs
6
BMS connector
7
Communication indicator LED
8
Confi guration indicator LED
Confi guration dipswitches
For correct communication with pRack pR300T, the dipswitches on the
expansion card should be confi gured as follows:
Address: 15
Ext: no off set
Baud: 19.2 K
Prot: CAREL
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
ON
OFF
Address
The pRack pR300T software (version 3.3.0 and higher) off ers the possibility
to extend the number of I/Os by expansion card directly from the Wizard,
in screen Ib1f:
Wizard
Enable I/O expansion
board management:
Copyright HPL March 2021
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
7
6
5
9
10
11
19.2 K
12
13
9.6 K
14
with offset
38.4 K
CAREL
15
no offset
57.6 K
Modbus
Ext.
Baud
Prot
3
2
Fig. 2.a
19.2 K
9.6 K
with offset
38.4 K
CAREL
no offset
57.6 K
Modbus
Ext.
Baud
Prot
Fig. 2.k
Ib1f
NO
Additional confi guration of the expansion card is possible on Fda01,
under PROGRAMMING
F.Settings
L1-Fieldbus
Enable cpCOe:
Offline pattern:
Digital output pattern
1:OFF
4:OFF
When enabling "Offl ine pattern", the status of the outputs can be
confi gured if the card is offl ine from the pRack.
Both the digital (Fda01) that analogue outputs (Fda02) can be confi gured
L1-Fieldbus
Univers.input pattern
UI01:--0%
UI03:--0%
UI05:--0%
UI07:--0%
UI09:--0%
Note:
the expansion card cannot be used to confi gure the suction
pressure probes (including the backup probes)
The expansion card is connected to the pRack pR300T via port J26 FBus
on the pRack, the same used for connecting an external driver, and port
J6BMS on the expansion card via RS485
Only one expansion card can be used for each compressor rack and the
expansion card can only be connected to the board with pLAN address 1:
20
Page 69 of 179
d.FIELDBUS:
Fda01
NO
DIS
2:OFF
3:OFF
5:OFF
6:OFF
Fda02
UI02:--0%
UI04:--0%
UI06:--0%
UI08:--0%
UI10:--0%
Fig. 2.l
Fig. 2.m
P41135 Rev 03