Daikin GCU2020PXB1 Installation, Commissioning And Maintenance Manual page 103

Table of Contents

Advertisement

ENG
Mask index
Display description
A. Unit status
Aa01 (display
Pressure
Sat.Temp.
only)
ActualSet
Diff eren.
Aa02 (display
Pressure
Sat.Temp.
only)
ActualSet
Diff eren.
Aa03 (display
Act/Req.
Reg. Status
only)
Reg. Type
Setpoint
Aa04 (display
C01, C02, ...C12
C01
only)
...
C12
Aa05 (display
Temperature
Superheat.
only)
Aa11 (display
Disch. 1
...
only)
Disch. 6
Aa12 (display
Oil Temp 1
...
only)
Oil Temp 6
Aa13 (display
In.liq.1: DO
only)
...
In.liq.6: DO
Aa15 (display
Discharge temperature
Cap.Reduction
only)
Oil sump T.
Oil status
Aa16 (display
Status
only)
Count
Compr.
Valve
Cap.Req.
ActualCapac.
Aa20 (display
Pressure
Sat.Temp.
only)
ActualSet
Diff eren
Aa21 (display
Pressure
Sat.Temp.
only)
ActualSet
Diff eren.
Aa22 (display
Act/Req
Reg. Status
only)
Reg. Type
Setpoint
Aa23 (display
F1
only)
...
F8
Aa24 (display
F9
only)
...
F16
Aa25 (display
Discharge temperature
External temperature
only)
Aa31 (display
Pressure
Sat.Temp.
only)
ActualSet
Diff eren.
Aa32 (display
Pressure
Sat.Temp.
only)
ActualSet
Diff eren.
Aa33 (display
Act/Req.
Reg. Status
only)
Reg. Type
Setpoint
Copyright HPL March 2021
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Description
Suction pressure (line 1)
Suction saturated temperature (line 1)
Actual setpoint for pressure regulation (with compensations applied, line 1)
Regulation diff erential for pressure regulation (line 1)
Suction pressure (line 1)
Suction saturated temperature (line 1)
Actual setpoint for temperature regulation (with compensations applied, line 1)
Regulation diff erential for temperature regulation (line 1)
Power delivered/Power requested per suction line (line 1)
Regulation status (according to the type of regulation set, line 1)
Compressor regulation type (line 1)
Actual suction setpoint (with compensations applied, line 1)
Time remaining for next compressor startup (line 1)
Power delivered from compressor 1 of line 1 (a "!" to the right of the value means that some
form of compressor power forcing is active, e.g., safety times, alarms, startup procedure)
...
Power delivered from compressor 12 (line 1)
Suction temperature (line 1)
Superheating (line 1)
Discharge temperature compressor 1 (line 1)
...
Discharge temperature compressor 6 (line 1)
Oil temperature compressor 1 (line 1)
...
Oil temperature compressor 6 (line 1)
Digital output number associated and liquid injection/economizer (*) status compressor 1
(line 1)
...
Digital output number associated and liquid injection/economizer (*) status compressor 6
(line 1)
Discharge temperature Digital Scroll
TM
compressor (line 1)
Capacity reduction Digital Scroll
TM
compressor (line 1) in progress
Oil sump temperature Digital Scroll
TM
compressor (line 1)
Oil dilution status Digital Scroll
TM
compressor (line 1)
Operational status Digital Scroll
TM
compressor (line 1)
TM
Safety time count Digital Scroll
compressor (line 1)
TM
Status Digital Scroll
compressor (line 1)
TM
Status Digital Scroll
valve (line 1)
TM
Capacity requested Digital Scroll
compressor (line 1)
TM
Actual capacity Digital Scroll
compressor (line 1)
Condensing pressure (line 1)
Condensing saturated temperature (line 1)
Actual setpoint for pressure regulation (with compensations applied, line 1)
Regulation diff erential for pressure regulation (line 1)
Condensing pressure (line 1)
Condensing saturated temperature (line 1)
Actual setpoint for temperature regulation (with compensations applied, line 1)
Regulation diff erential for temperature regulation (line 1)
Power delivered/Power requested per condensing line (line 1)
Regulation status (according to the type of regulation set, line 1)
Gas cooler regulation type (line 1)
Actual setpoint gas cooler (line 1)
Power delivered from fan 1 of line 1 (a "!" to the right of the value means that some form of
power forcing is active)
...
Power delivered from fan 8 of line 1 (a "!" to the right of the value means that some form of
power forcing is active)
Power delivered from fan 9 of line 1 (a "!" to the right of the value means that some form of
power forcing is active)
...
Power delivered from fan 16 of line 1 (a "!" to the right of the value means that some form of
power forcing is active)
Discharge temperature (line 1)
External temperature (line 1)
Suction pressure (line 2)
Suction saturated temperature (line 2)
Actual setpoint for pressure regulation (with compensations applied, line 2)
Regulation diff erential for pressure regulation (line 2)
Suction pressure (line 2)
Suction saturated temperature (line 2)
Actual setpoint for temperature regulation (with compensations applied, line 2)
Regulation diff erential for temperature regulation (line 2)
Power delivered/Power requested per suction line (line 2)
Regulation status (according to the type of regulation set, line 2)
Compressor regulation type (line 2)
Actual suction setpoint (with compensations applied, line 2)
54
Page 103 of 179
Def.
U. of M.
Values
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
%
0 | 0 ...100 | 100
---
---
Stop | Increase
Decrease
Stand-by
Functioning
Timings | Alarms
---
---
Proportional Band
Dead Zone
---
...
...(**)
---
s
0...32000
---
%
0...100
...
...
...
---
%
0...100
---
...
...(**)
---
...
...(**)
---
...
...(**)
...
...
...
---
...
...(**)
---
...
...(**)
...
...
...
---
...
...(**)
---
...
0...29
...
...
...
---
...
0...29
---
...
...(**)
NO | YES
---
...
...(**)
OK | Diluted
---
---
OFF | Start
ON | Alarm
---
s
0...999
---
---
ON | OFF
---
---
ON | OFF
---
%
0...100
---
%
0...100
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
%
0 | 0 ...100 | 100
---
---
Stop | Increase
Decrease
Stand-by
Functioning
Timings | Alarms
---
---
Proportional Band
Dead Zone
---
...
...(**)
---
%
0...100
...
...
...
---
%
0...100
---
%
0...100
...
...
...
---
%
0...100
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
...
...(**)
---
%
0 | 0 ...100 | 100
---
---
Stop | Increase
Decrease
Stand-by
Functioning
Timings | Alarms
---
---
Proportional Band
Dead Zone
---
...
...(**)
P41135 Rev 03