Daikin GCU2020PXB1 Installation, Commissioning And Maintenance Manual page 61

Table of Contents

Advertisement

ENG
2.2.9
Serial port
Use AWG 20-22 twisted pair shielded cable for the +/-
Serial
Type/connectors
Serial ZERO
pLAN/J10, J11
Serial ONE
BMS 1 Serial Card
Serial TWO
FieldBus 1 Serial Card • Not integrated on main board
Serial THREE
BMS 2 / J25
Serial FOUR
FFieldBus 2 / J26 (and
J23 on Large and
Extralarge version)
Note: in industrial/residential environments, for distances > 10 m, shielded cable is required, with the shield connected to earth. In residential environments (EN
55014), irrespective of the cable length, on versions without valve driver, the connection cable between the controller and the terminal and the serial cable must be
shielded and connected to earth at both ends.
2.2.10 Model with electronic expansion valve driver
CAREL: E*V****
ALCO: EX4; EX5; EX6; EX7; EX8 330 Hz (recommended by CAREL); EX8 500 Hz (from ALCO specifi cations)
SPORLAN: SEI 0.5-11; SER 1.5-20; SEI 30; SEI 50; SEH 100; SEH175
Valve compatibility
Danfoss: ETS 12.5-25B; ETS 50B; ETS 100B; ETS 250; ETS 400 CCM 40, CCM 10-20-30, CCMT 2-4-8
CAREL: two CAREL EXV as for EVD EVOLUTION TWIN
SPORLAN: SER(I) G, J, K
Shielded 4-wire cable CAREL P/N E2VCABS*00, or AWG22 shielded 4-wire cable Lmax =10 m,
Motor connection
or AWG14 shielded 4-wire cable Lmax 50 m
Digital input
Digital input to be activated with voltage-free contact or transistor to GND.
connection
Closing current 5mA; maximum length < 10 m
Maximum length 10 m or less than 30 m with shielded cable
S1 ratiometric pressure probe (0 to 5 V)
electronic pressure sensor (4 to 20 mA)
combined ratiometric pressure probe (0 to 5 V) resolution 0.1 % fs
4 to 20 mA input (max. 24 mA)
S2 low temperature NTC
high temperature NTC
combined NTC
Probes
0 to 10 V input (max 12 V)
S3 ratiometric pressure probe (0 to 5 V):
electronic pressure sensor (4 to 20 mA)
combined ratiometric pressure probe (0 to 5 V) resolution 0.1 % fs
4 to 20 mA input (max. 24 mA)
S4 low temperature NTC
high temperature NTC
combined NTC
Power to active
programmable output: +5 Vdc ±2% or 12 Vdc ±10%, Imax = 50 mA
probes (VREF)
optional Ultracapacitor module (PCOS00UC20 or EVD0000UC0). If the controller operates constantly at temperatures near the upper limit of
Emergency power
60°C it's recommended to use the external module EVD0000UC0, where possible located in the coolest point of the panel. The PCOS00UC20
supply
and EVD0000UC0 modules can be connected at the same time to the same controller, thus doubling the energy available to close the valves.
Important: The module only powers the valve driver and not the controller.
Copyright HPL March 2021
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Features
• Integrated on main board
• HW driver: asynchronous half duplex RS485 pLAN
• Not optically-isolated
• Connectors: 6-pin telephone jack + 3-pin plug-in p. 5.08
• Maximum length: 500 m
• Max data rate: 115200 bit/s
• Maximum number of connectable devices: 3
• Not integrated on main board
• HW driver: not featured
• Can be used with all pCO family optional BMS cards
• HW driver: not present
• Can be used with all pCO family optional FieldBus cards
• Integrated on main board
• HW driver: asynchronous half duplex RS485 Slave
• Optically-isolated
• 3-pin plug-in connector p. 5.08
• Maximum length: 1000 m
• Max data rate: 384000 bit/s
• Integrated on main board
• J23: not optically-isolated
• J26: optically-isolated
• 3-pin plug-in connector p. 5.08
• J23 and J26 are independent.
resolution 0.1 % fs
resolution 0.5 % fs
resolution 0.5 % fs
10 kΩ at 25 °C, -50T90 °C
50 kΩ at 25 °C,-40T150 °C measurement error: 1.5 °C in the range -20T115°C, 4 °C in range
10 kΩ at 25 °C,-40T120 °C measurement error: 1°C in the range -40T50 °C; 3°C in the range
resolution 0.1 % fs
resolution 0.1 % fs
resolution 0.5 % fs
resolution 0.5 % fs
10 kΩ at 25 °C,-50T105 °C measurement error: 1 °C in the range -50T50 °C; 3°C in the range
10 kΩ at 25 °C,-40T150 °C measurement error: 1.5 °C in the range -20T115 °C; 4 °C in range
10 kΩ at 25 °C, -40T120 °C measurement error 1 °C in the range -40T50 °C; 3°C in the range
measurement error: 2% fs massimo; 1% typical
measurement error: 8% fs massimo; 7% typical
measurement error: 2 % fs massimo; 1 % typical
measurement error: 8 % fs massimo; 7 % typical
measurement error: 1°C in the range -50T50 °C; 3°C in the range
+50T90 °C
outside of -20T115 °C
+50T90 °C
measurement error: 9% fs massimo; 8% typical
measurement error: 2% fs massimo; 1% typical
measurement error: 8% fs massimo; 7% typical
measurement error: 2 % fs massimo; 1 % typical
measurement error: 8 % fs massimo; 7 % typical
50T90 °C
outside of -20T115 °C
+50T90 °C
12
Page 61 of 179
Tab. 2.l
Tab. 2.m
P41135 Rev 03