MASK
INDEX
DESCRIPTION
Cbb08
L2
Decreasing zone differential for compressors regulation (neutral zone)
Cbf11
L2
Sequence of load unloader
Cbb12
L2
Compressors neutral zone minimum complete activation time (neutral zone)
Cbb12
L2
Compressors neutral zone maximum complete activation time (neutral zone)
Cbb13
L2
Compressors neutral zone minimum complete deactivation time (neutral zone)
Cbb13
L2
Compressors neutral zone maximum complete deactivation time (neutral zone)
Cbb20
--
Cbb20
--
Cbd08
L2
Enable floating suction setpoint compensation
Cbd09
L2
Floating suction maximum setpoint
Cbd09
L2
Floating suction minimum setpoint
Cbd10
L2
Floating suction maximum delta admitted
Cbf02
L2
Compressors type
Cbf02
L2
Number of compressors
Cbf04
L2
Suction refrigerant type
Cbf10
L2
Compressors rotation type
Cbf15
L2
Compressors modulating device type
Cbf40
L2
Have compressors different size? {0=Equal - 1=Different}
Cbf40
L2
Have compressors different number of valves? {0=Equal - 1=Different}
Cbf41
L2
Compressors size 1
Cbf41
L2
Compressors size 2
Cbf41
L2
Compressors size 3
Cbf41
L2
Compressors size 4
Cbf42
L2
Stages configuration for compressor size 1
Cbf42
L2
Stages configuration for compressor size 2
Cbf42
L2
Stages configuration for compressor size 3
Cbf42
L2
Stages configuration for compressor size 4
Cbf16
L2
Compressors inverter minimum frequency
Cbf16
L2
Compressors inverter maximum frequency
Cbg01
L2
Compressors inverter minimum voltage
Cbg01
L2
Compressors inverter maximum voltage
Cbg01
L2
Compressors inverter nominal frequency
Cbg01
L2
Compressors inverter nominal power
Cbg02
L2
Compressors inverter rising time
Cbg02
L2
Compressors inverter falling time
Cbg05
L2
Regulation value in case of all regulation probe fault
Cbd05
L2
Function for setpoint compensation by digital input enabled (suct/cond)
Dbb01
L2
Fans regulation type
Dbb01
L2
Fans control mode
Dbb02
L2
Minimum Intercooler setpoint
Dbb02
L2
Maximum Intercooler setpoint
Dbb03
L2
Intercooler setpoint
Dbb04
L2
Fan can work only when at least one compressor work
Dbb06
L2
Cond. - Regulation type (P - P+I - PID)
Dbb06
L2
Cond. - Integral time
Dbb14
L2
Intercooler neutral zone minimum complete activation time (neutral zone)
Dbb14
L2
Intercooler neutral zone maximum complete activation time (neutral zone)
Dbb15
L2
Intercooler neutral zone minimum complete deactivation time (neutral zone)
Copyright HPL March 2021
VALUE
UOM
TYPE
0
barg
2
CpppCppp
15
sec
90
sec
30
sec
180
sec
--
--
0
N.O.
40
barg
0
barg
1
barg
0
RECIPROCATING
3
10
1
FIFO
0
NONE
0
N.O.
0
N.O.
10
kW
10
kW
10
kW
10
kW
0
100
0
100
0
100
0
100
30
Hz
60
Hz
0
V
10
V
50
Hz
10
kW
20
sec
20
sec
0
%
0
N.O.
0
PROPORTIONAL BAND
1
TEMPERATURE
5
°C
25
°C
25
°C
0
N.O.
0
PROPORTIONAL
0
sec
15
sec
90
sec
30
sec
Page 4 of 16
CHANNEL
MIN
MAX
OFFSET
Page 149 of 179
FULL CAREL PARAMETERS LIST