Daikin GCU2020PXB1 Installation, Commissioning And Maintenance Manual page 108

Table of Contents

Advertisement

Mask index
Display description
Bbb06
Oil cool. pump
Force to
Bbb07
Compressor 1
Force to
Bbb08
Oil cool. pump
Force to
Bbb09
Fan 1
Force to
Bbb10
Heat recovery pump
Force to
Bbb11
Fan 1
Force to
Bbb12
Heat recovery pump
Force to
Bbb75
---
---
--- (display only)
Max limit
Min limit
Calibrat.
Bc01
Test DO
Timeout
Bc02
Test AO
Timeout
Bca10
DO1
---
...
...
Bca26
D29
---
Bcb10
AO1
...
...
Bcb12
AO6
Mask index
Display description
C.CompressorS
The I/Os depend on the confi guration selected, the following are only examples. See Appendix A.1 for the complete list and position of available I/Os.
Caa01
DI
Status (display only)
Logic
Function (display only)
...
...
Caa08
Line relay DO
Part winding DO/Star relay
DO (*)
---/Delta relay DO (*)
Logic
Caa09
DO
Status (display only)
Logic
Function (display only)
...
...
Caa14
AO
Status (display only)
...
...
Caaal
---
---
--- (display only)
Max limit
Min limit
Calibrat.
...
...
Cab01
Regulation
Reg. Type
Cab02
Minimum
Maximum
Cab03
Setpoint
Cab04/Cab6 (**) Reg. Type
Integral time
Cab05/Cab7 (**) Diff erential
Cab08/Cab10 (**) NZ diff .
Activ.diff .
Deact.diff .
Cab09/Cab11 (**) En.force off
Setp. force off
Cab12
Power to 100%
min time
Power to 100%
max time
Copyright HPL March 2021
Description
Manual request for oil cooling pump (line 1)
Manual request for continuous capacity for compressor 1 (line 2)
Manual request for oil cooling pump (line 2)
Manual request for continuous capacity for fan 1 (line 1)
Manual request for heat recovery pump (line 1)
Manual request for continuous capacity for fan 1 (line 2)
Manual request for heat recovery pump (line 2)
Discharge pressure probe position (line 2)
Discharge pressure probe type (line 2)
Discharge pressure value (line 2)
Maximum discharge pressure value (line 2)
Minimum discharge pressure value (line 2)
Common oil receiver pressure probe calibration (line 2)
Enable DO test mode
Duration of test mode after last key pressed
Enable AO test mode
Duration of test mode after last key pressed
DO 1 test logic
DO 1 test value
...
DO 29 test logic
DO 29 test value
AO 1 test value
...
AO 6 test value
Description
Alarm 1 compressor 1 DI position (line 1)
Status Alarm 1 compressor 1 DI (line 1)
Logic alarm 1 compressor 1 DI (line 1)
Alarm 1 compressor 1 function status (line 1)
...
Compressor 1 line DO position and status (On/Off ) display (line 1)
Compressor 1 part winding/star DO position and status (On/Off ) display
(line 1)
Compressor 1 DO position and status (On/Off ) display (line 1)
Logic for compressor 1 power supply DO (line 1)
Compressor 1 unloader 1 DO position (line 1)
Status for compressor 1 unloader 1 DO (line 1)
Logic for compressor 1 unloader 1 DO (line 1)
Compressor 1 unloader 1 function status (line 1)
...
Compressor modulating device AO position (line 1)
Modulating device output value (line 1)
...
Suction pressure probe position (Line 1)
Suction pressure probe type (Line 1)
Suction pressure value (line 1)
Suction pressure maximum value (line 1)
Suction pressure minimum value (line 1)
Suction pressure probe calibration (Line 1)
...
Compressor control by temperature or pressure (line 1)
Compressor regulation type (line 1)
Compressor setpoint lower limit (line 1)
Compressor setpoint upper limit (line 1)
Compressor setpoint (line 1)
Proportional regulation type (line 1)
Integral time for proportional regulation (line 1)
Diff erential for proportional regulation (line 1)
Dead zone regulation diff erential (line 1)
Dead zone regulation diff erential for device activation (line 1)
Dead zone regulation diff erential for device deactivation (line 1)
Enable capacity immediate decreasing to 0 (line 1)
Threshold for capacity decreasing to 0 (line 1)
Minimum time to increase capacity request to 100%, dead zone regulation
(suction line 1)
Maximum time to increase capacity request to 100%, dead zone regulation
(suction line 1)
59
Page 108 of 179
Def.
U. of M.
Values
0.0
%
0.0...100.0
0.0
%
0.0...100.0
0.0
%
0.0...100.0
0.0
%
0.0...100.0
0.0
%
0.0...100.0
0.0
%
0.0...100.0
0.0
%
0.0...100.0
---
---
U1...U10 (****)
4...20mA
---
----, 0-1V
0-10V
4...20mA
0-5V
---
...
...(**)
44.8 barg
...
...(**)
0.0 barg
...
...(**)
0.0 barg
...
...(**)
NO
---
NO | YES
10
min
0...500
NO
---
NO | YES
10
min
0...500
NO
---
NO | NC
OFF
---
OFF | ON
...
...
...
NO
---
NO | NC
OFF
---
OFF | ON
0.0
---
0.0...100.0
...
...
...
0.0
---
0.0...100.0
Def.
U. of M.
Values
03
---
--- | 01...18 |
U1...U10 (****)
---
---
closed | open
NC
---
NC | NO
---
---
not active | active
...
...
...
...
---
---, 01...18 (****)
...
---
---, 01...18 (****)
...
---
---, 01...18 (****)
NC
---
NC | NO
...
---
---, 01...18 (****)
---
---
closed | open
NC
---
NC | NO
---
---
not active | active
...
...
...
0
---
---, 01...06 (****)
0
%
0.0...100.0
...
...
...
B1
---
--- | U1...U10 (****)
4...20 mA
---
----
0-1 V
0-10 V
4...20 mA
0-5 V
---
...
...(**)
44.8 barg
...
...(**)
0.0 barg
...
...(**)
0.0 barg
...
...(**)
...
...
...
pressure
---
pressure
temperature
dead zone ---
proportional Band
dead Zone
0.0 barg
...
...(**)
40.0 barg
...
...(**)
26.0 barg
...
...(**)
proporz.
---
proportional /
proport.+int.
300
s
0...999
0.5 barg
...
...(**)
0.5 barg
...
...(**)
0.7 barg
...
...(**)
0.7 barg
...
...(**)
NO
---
NO | YES
0.0 barg
...
...(**)
15
s
0...9999
90
s
0...9999
P41135 Rev 03
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017