Daikin GCU2020PXB1 Installation, Commissioning And Maintenance Manual page 151

Table of Contents

Advertisement

MASK
INDEX
DESCRIPTION
Cbe07
L2
Low superheat alarm threshold
Cbe07
L2
Low superheat alarm differential
Cbe07
--
Cbe07
L2
Superheat Alarm manual or automatic reset
Cbe07
L2
Low superheat alarm delay
Cbe35
L2
Discharge threshold setpoint
Cbe35
L2
Discharge threshold differential
Cbe35
L2
Enable the switch off of the compressor when its high discharge temperature alarm occurs
Cbe36
L2
Relative discharge setpoint high alarm
Cbe36
L2
High discharge pressure alarm threshold
Cbe37
L2
High discharge pressure alarm differential
Cbe37
L2
High discharge pressure alarm delay
Gcb01
L2
Common HP alarm type
Gcb01
L2
High common condensing pressure delay
Gcb02
L2
Low common condensing pressure start delay
Gcb02
L2
Low common condensing pressure delay
Gcb03
L2
Time for lock compressor during low pressure
Gcb03
L2
Number of tries before become manual
Gba01
L2
Enable high condensing pressure prevent
Gba01
--
Gba02
--
Gba02
--
Gba02
--
Gba06
--
Gba06
--
Gba06
--
EVS
--
Eia02
--
Eia02
--
Eia02
--
Eia02
--
Eia04
--
Eia04
--
Eia04
--
Eia04
--
Eif01
--
Eif01
--
Eif02
--
Eif15
--
Bab01
L1
Suction pressure
Bab70
--
Bab02
L1
Suction pressure backup
Bab03
L1
Suction temperature
Bab04
L1
condensing pressure
Bab09
L1
condensing pressure backup
Bab10
--
Bab11
L1
Discharge temperature
Bab12
L1
condensing outlet temperature
Copyright HPL March 2021
VALUE
UOM
TYPE
3
K
1
K
--
0
MANUAL
30
sec
85
°C
5
°C
0
N.O.
0
°C
35
barg
5
barg
0
sec
0
AUTO
1
sec
60
sec
20
sec
120
min
5
0
N.O.
--
--
°C
--
°C
--
sec
--
°C
--
°C
--
sec
--
--
K
--
K
--
°C
--
°C
--
K
--
K
--
°C
--
°C
--
--
--
--
0
barg
4-20mA
--
°C
0
°C
4-20mA
0
°C
NTC
0
barg
4-20mA
0
barg
4-20mA
--
A
0
°C
HTNTC
0
°C
HTNTC
Page 6 of 16
CHANNEL
MIN
MAX
OFFSET
U1
0
0
U4
0
U2
0
U2
0
U5
0
U6
0
Page 151 of 179
FULL CAREL PARAMETERS LIST
HPL
ADJUSTED
Last Printed: 05/02/2020
P41135 Rev 03