View of output busbar connections of frame size R7 (DC and brake busbars included)

WARNING! The output busbars are fastened to the insulating supports with M8x16 screws
when no cable lug terminal is connected, but with M8x20 screws when a cable lug terminal
is also connected with the same screw. Screwing an M8x20 screw without a cable lug
terminal through the busbar into the insulating support will break the insulating support.
Fasten the cable lug terminals elsewhere with M10x25 screws.
2
2
2
2
M8
1
2
2
2
2
2
2
Mechanical installation of pre-assembled units (ACS800-04/U4)
Top view of insulating support and cable
lug terminal connections
M8x16
Cable lug
terminal
2
2
M10x30
Tightened at the factory
Insulating support
M8x20
Tightening torques
M8: 15...22 Nm (3.7 lbf ft)
M10: 30...44 Nm (22...32 lbf ft)
Spring washer with
Nut
mechanically sprayed zinc
coating
Plain washer with
electroplated zinc coating
and yellow chromate
passivation