Drive module of frame size R7 with bottom exit

What this chapter contains

This chapter describes the installation of a drive module of frame size R7 with
bottom exit into a 600 mm deep, 800 mm wide and 2000 mm high Rittal TS 8
enclosure. The installation is designed to comply with the limits of IEC/EN 61800-3
for immunity and emissions of electrical equipment in first environment (includes
establishments connected to a low-voltage network which supplies buildings used
for domestic purposes). This requires EMC screen and EMC cable lead-throughs,
which are otherwise not necessarily needed. The installer is responsible for the
verification. The degree of protection of the installaton is IP20.

Rittal parts

This table lists the Rittal parts used in the installation.
Rittal model no.
Description
TS 8806.500
Enclosure with mounting plate, width × height × depth: 800 mm × 2000 mm × 600 mm
TS 8106.235
Side panel for 2000 mm × 600 mm
TS 8612.160
Punched section with mounting flange, outer mounting level for 600 mm horizontal
TS 8614.240
Mounting plate 1100 mm × 300 mm
DK 7092.000
C-rail 390 mm
DK 7097.000
C-rail cable clamp for cable diameters of 18 to 22 mm
DK 7098.000
C-rail cable clamp for cable diameters of 38 to 42 mm
DK 7828.060
C-rail 600 mm
DK 7967.000
50 mm spacer for roof plate
PS 4944.000
Support rail 555 mm
SK 3326.267 *
EMC compatible air filter 323 mm for 292 mm × 292 mm door ventilation holes
SK 3326.607
EMC compatible fan-and-air-filter unit 700/720 m
SV 3568.000
Laminated copper bar Flexibar S. Dimensions: 15.5 mm × 4.8 mm, 2000 mm long
*
for first environment EMC installations. In other installations SK 3326.200 air filter 323 mm for
292 mm × 292 mm door ventilation holes can be used.
For photos and specifications of the parts, refer to www.rittal.com.

ACS800-04M parts

The following ACS800-04M parts are used in the installation:
• drive module of type ACS800-04M-xxxx+B060+E202+H352+J400+J410. For
descriptions of the plus codes, refer to ACS800-04/04M/U4 Cabinet Installation
[3AFE68360323 (English)], chapter The ACS800-04/U4 and ACS800-04M: Type
code.
3
/h, 230 V, 50/60 Hz
Drive module of frame size R7 with bottom exit
11
Qty
(pcs)
1
2
2
1
1
4
6
2
4
1
3
1
3

Advertisement