Instructions specific to hazardous area
(Reference European ATEX Directive 94/9/EC,
The following instructions apply to equipment covered by certificate number SIRA
03ATEX2142X:
1.
For use and assembly, refer to the main instructions.
2.
The equipment is certified for use as Category 1GD equipment.
3.
The equipment may be used with flammable gases and vapors with apparatus group
IIC and temperature class T4.
4.
The equipment is certified for use in an ambient temperature range of –40 °C to
80 °C.
5.
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6.
Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and
EN 60079-17 in Europe).
7.
Repair of this equipment shall be carried out by suitably trained personnel in
accordance with the applicable code of practice (e.g. EN 60079-19 within Europe).
8.
Components to be incorporated into or used as replacements in the equipment shall
be fitted by suitably trained personnel in accordance with the manufacturer's
documentation.
9.
The 'X' suffix to the certificate number relates to the following special conditions for
safe use:
a. Parts of the enclosure may be non-conducting and may generate an ignition-
capable level of electrostatic charge under certain extreme conditions. The user
should ensure that the equipment is not installed in a location where it may be
subjected to external influences which might cause a build-up of electrostatic
charge on non-conducting surfaces.
b. As either Aluminum, Magnesium, Titanium or Zirconium may be used at the
accessible surface of the equipment, in the event of rare incidents, ignition
sources due to impact and friction sparks could occur. This shall be considered
when the SITRANS LR 250 is being installed in locations that specifically require
group II, category 1G equipment.
7ML19985JE01
installations
Annex II, 1/0/6)
SITRANS LR250 (HART) – INSTRUCTION MANUAL
(continued on next page)