Wiring Setups For Hazardous Area Installations; Intrinsically Safe Wiring - Siemens SITRANS LR250 Instruction Manual

Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

1.
Strip the cable jacket for approximately 70 mm
(2.75") from the end of the cable, and thread
the wires through the gland
2.
Connect the wires to the terminals as shown:
the polarity is identified on the terminal block.
3.
Ground the instrument according to local
regulations.
4.
Tighten the gland to form a good seal.
Wiring setups for hazardous
area installations
There are five wiring options for hazardous area installations. In all cases, check the
nameplate on your instrument, and confirm the approval rating.

1. Intrinsically Safe wiring

SITRANS LR 250
7ML1234-56789-0ABC-D
Serial No: GYZ / S1034567
Encl.: NEMA / TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40 °C to 80 °C
Power Rating: 24V
Nom., 30 V
Siemens Milltronics Process Instruments Inc., Peterborough
Made in Canada
SITRANS LR 250
7ML1234-56789-0ABC-D
Serial No: GYZ / S1034567
Encl.: NEMA / TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40 °C to 80 °C
Power Rating: 24V
Nom., 30 V
Siemens Milltronics Process Instruments Inc., Peterborough
ATEX II 1 G, EEx ia IIC T4
ATEX II 1 D, EEx tD A20 IP67 T90 °C
IECEx SIR 05.0031X, Ex ia IIC T4, Ex tD A20 IP67 T90 °C
FM/CSA:
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class III
1.
If cable is routed through conduit, use only approved suitable-size hubs for
waterproof applications.
7ML19985JE01
1
.
Max., 4 - 20mA
Max., 4 - 20mA
Made in Canada
Approval Rating
SITRANS LR250 (HART) – INSTRUCTION MANUAL
Ii = 120 mA
II 1 D IP68 Txx
Ui = 30V
II 1 G EEx ia IIC T4
Li = 0.1mH
03ATEX2142X
SIRA
Pi = 0.8W
IECEx SIR 05.0031X
Ci = 15nF
Ex ia IIC T4
HART
WARNING: Possible Static Hazard, Do Not Rub Or Clean On Site.
CANADA: 267P - LR 250
FCC ID: NJA - LR 250
Exia per drawing: 23650653
Temp. Code : T4
Class I, Div1,Group A,B,C,D
I max = 120mA
Class II, Div1,Group G
P max = 0.8 W
Class III
V max = 30V
C i = 15 nF
HART
L i = 0.1 mH
WARNING: Possible Static Hazard, Do Not Rub Or Clean On Site.
Valid for:
Europe
International
US/Canada
cable shield
(if used)
R
Page 25