Appendix C: Troubleshooting

Communication Troubleshooting

Generally:

1.
Check the following:
There is power at the instrument
The LCD shows the relevant data
The device can be programmed using the hand programmer
2.
Verify that the wiring connections are correct.
3.
If you continue to experience problems, go to our website at:
.
www.siemens.com/processautomation, and check the FAQs for SITRANS LR250, or
contact your local Siemens Milltronics representative.

Specifically:

1.
If you try to set a SITRANS LR250 parameter via remote communications, but the
parameter remains unchanged:
Some parameters can only be changed when the device is not scanning. Try
putting the device in PROGRAM mode using the operating mode function.
Try setting the parameter from the keypad. (First make sure that the lock
parameter [6.1] is set to the unlock value.)
The communications control parameter 5.2 must be set to 1 to allow you to write
parameters to SITRANS LR250.
2.
If you see unanticipated displays, for example:
PROGRAM mode displayed instead of Measurement mode
the wrong parameter displayed in response to a command
a parameter displayed in response to no command
make sure no infrared-capable device is close to SITRANS LR250. Any device with
infrared capabilities (laptops, cell phones, PDAs) can cause interference which
simulates a command to the SITRANS LR250, potentially causing it to switch modes
or to change a parameter.
3.
If the operation is erratic, make sure the Hand Programmer is not being used at the
same time as SIMATIC PDM.
7ML19985JE01
SITRANS LR250 (HART) – INSTRUCTION MANUAL
Page 97