Appendix C: Troubleshooting
Communication Troubleshooting
Generally:
1.
Check the following:
•
There is power at the instrument
•
The LCD shows the relevant data
•
The device can be programmed using the hand programmer
2.
Verify that the wiring connections are correct.
3.
If you continue to experience problems, go to our website at:
.
www.siemens.com/processautomation, and check the FAQs for SITRANS LR250, or
contact your local Siemens Milltronics representative.
Specifically:
1.
If you try to set a SITRANS LR250 parameter via remote communications, but the
parameter remains unchanged:
•
Some parameters can only be changed when the device is not scanning. Try
putting the device in PROGRAM mode using the operating mode function.
•
Try setting the parameter from the keypad. (First make sure that the lock
parameter [6.1] is set to the unlock value.)
•
The communications control parameter 5.2 must be set to 1 to allow you to write
parameters to SITRANS LR250.
2.
If you see unanticipated displays, for example:
•
PROGRAM mode displayed instead of Measurement mode
•
the wrong parameter displayed in response to a command
•
a parameter displayed in response to no command
make sure no infrared-capable device is close to SITRANS LR250. Any device with
infrared capabilities (laptops, cell phones, PDAs) can cause interference which
simulates a command to the SITRANS LR250, potentially causing it to switch modes
or to change a parameter.
3.
If the operation is erratic, make sure the Hand Programmer is not being used at the
same time as SIMATIC PDM.
7ML19985JE01
SITRANS LR250 (HART) – INSTRUCTION MANUAL
Page 97